D/E/F 5.601.B.6/1
1.15
13
E
6. DIMENSIONS
See brochure, technical data sheet or design software.
7. HYDRAULIC CONNECTION
Dimension of the cooler element connection:
G3/4
(PTK-200/-250/-300/-350)
When mounting or dismantling the threaded connection of the cooler
element inlet or outlet, the torque must be counteracted at the hexagon
using a suitable tool
(see diagram)
To protect the cooler element from distortions
Protect the connections of the cooler element from the torque:
M max. 40Nm
Connecting lines (not supplied) must be such that any oscillations,
stresses or knocks do not affect the cooler element.
If possible do not reduce pipe cross-sections pre-determined by the
threaded connections.
8. THREADED CONNECTIONS IN THE OPERATING
FLUID CIRCUIT
The connections must not be sealed with Teflon tape or adhesive,
to ensure ingress into the cooling system does not occur.
Only threaded connections to DIN3852-T11 Form E with profile seal ring
must be used.
IMPORTANT
INFORMATION
IMPORTANT