FluidAqua Mobil - FAM 10
Clean the suction screen
HYDAC FILTER SYSTEMS GMBH
en(us)
Page 65 / 72
BEWA FAM10 3102456f en-us 2012-03-13.doc
2012-03-13
11. Push the tensioning clamp (1) up around the
filter bowl over the bead on the filter bowl /
filter head.
Tighten the tensioning clamp with a 6 mm
Allen wrench in a clockwise direction.
The tightening torque is 5 Nm.
12. Check that the drain plug on the filter bowl is
secure.
13. The filter element change is now complete.
After commissioning, check the filtration unit
for leaks.
Checking the settings on the heater (optional)
Under normal operating conditions the heater element is maintenance-free.