Configuration menu
FAM 5
en-US
Page 73 / 148
BEWA FAM5 4166129a en-us 2019-03-04.docx
2019-03-04
Configuration menu
The configuration menu is used to determine which optional components
have been installed.
Configuration is only required:
•
After loading a new program/language version.
•
To deactivate a defective component.
After loading a new program version to the PLC, the display automatically
switches to the Configuration menu.
To go to the Configuration menu from other menus, simultaneously press:
1.
ESC + up ▲ arrow key
2.
ESC + down ▼ arrow
key
Description
AS1000
detected
AquaSensor AS1000 detected:
FAM-5-x-x-x-xx-x-x-S-
A/AC/ACS
-x
CS1000
detected
ContaminationSensor CS 1000 detected:
FAM-5-x-x-x-xx-x-x-S-
AC/ACS
-x
Heater
detected
Heated detected: FAM-5-x-x-x-xx-x-
H
-S-x-x
The individual components can have the following statuses:
•
OFF: Inactive / not detected
•
ON: Active / detected
HARDWARE CONFIG
AS1000 detected
CS1000 detected
Heater detected
1.
2.