TransformerCare Unit
Troubleshooting and measures after an alarm/failure
Setting the differential pressure relief valve
B
A
7
18
Proceed as follows to set the differential pressure relief valve:
1.
Pull of the black lid on the differential pressure relief valve.
2.
Undo the counternut (B) with a size 19 screw wrench.
3.
Set the required pressure of 18 bar on the setscrew (A) using a screwdriver.
4.
Tighten the counternut (B), holding the setscrew (A) in the correct position.
5.
Replace the black lid onto the differential pressure relief valve.
HYDAC FILTER SYSTEMS GMBH
en
Page 58 / 64
BeWa TCU 3472805b en 2011-07-05.doc
2011-07-05