20
ETS 3000 IO-Link
Edition: 2016-08-18
HYDAC
ELECTRONIC
GMBH
Part No.: 669904
15.2 ETS 3800 FOR EXTERNAL SENSOR PROBE
Input data
Measurement element
PT 100 (TFP 100)
Measuring range
-30 .. 150 °C (-22 .. 302 °F)
Connection
(separate temperature probe)
Female cable connection M12x1, 4 pole
Output data
Switching outputs
PNP- transistor outputs
Switching current: max. 250 mA per output
(ohmic resistance)
Switching cycles: > 100 million
Analogue output,
permitted load resistance
Selectable:
4 .. 20 mA
ohmic resistance max. 500
Ω
0 .. 10 V
ohmic resistance min. 1 k
Ω
corresponds in each case to -30 .. +150 °C
Accuracy (at room temperature)
≤
± 1,0 °C (
≤
± 2,0 °F)
( + separate temperature probe error)
Temperature drift (ambient)
≤
± 0,015 % FS / °C (
≤
± 0,0085 % FS / °F)
Repeatability
≤
± 0,25 % FS max.
Environmental conditions
Operating temperature range
-25 .. + 80 °C (-13 .. 176 °F)
(-25 .. +60 °C [ -13 .. +140 °F] acc. to UL spez.)
Storage temperature range
-40 .. + 80 °C (-40 .. 176 °F)
- mark
EN 61000-6-1 / 2 / 3 / 4
- mark
2)
Certifikat-No.: E318391
Vibration resistance to
DIN EN 60068-2-6 bei 0 .. 500 Hz
≤
10 g
Shock resistance to
DIN EN 60068-2-27 (11 ms)
≤
50 g
Protection class to DIN EN 60529
3)
IP 67
1 Other
data
Supply voltage
for use acc. to UL spec.
9 .. 35 V DC if PIN2 = SP2
18 .. 35 V DC if PIN2 = analogue output
- limited energy- acc. to 9.3 UL 61010; Class 2;
UL 1310/1585; LPS UL 60950
Residual ripple of supply voltage
≤
5 %
Current consumption
≤
0,535 A
with active switching outputs
≤
35 mA
with inactive switching outputs
≤
55 mA
with inactive switching output and
analogue
output
Display
4-digit, LED, 7-segment, red, character height: 7 mm
Weight
̴
87 g (excluding connector and probe)
Note: Reverse polarity protection of the supply voltage, excess voltage, override,
short circuit protection are provided.
FS
(
F
ull
S
cale) = in relation to the full measurement range
1)
Depending on the temperature range of the temperature sensor fitted, the indication range
of the ETS 3000 may be reduced.
2)
Environmental conditions to 1.4.2 UL 61010-1; C22.2 No. 61010-1
3)
With mounted coupling box with appropriate protection
Содержание ETS 3000
Страница 30: ...Notizen Notes Notes ...
Страница 60: ...Notizen Notes Notes ...
Страница 90: ...Notizen Notes Notes ...
Страница 91: ...Notizen Notes Notes ...
Страница 92: ...Notizen Notes Notes ...