EDS 820 IO-Link
11
Edition: 2016-01-13
HYDAC
ELECTRONIC
GMBH
Part No.: 669916
E
11 Technical Data
Input data
Measuring Ranges
bar
16
25 40
60
100
250
400
600
Overload range
bar
32
50 80
120
200
500
800 1000
Burst pressures
bar
80
100 200
300
500 1250 2000 2000
Measuring Ranges
psi
500
1000
3000
6000
9000
Overload range
psi
1160
2900
7250
11600
14500
Burst pressures
psi
2900
7250
14500
29000
29000
Mechanical connection
G 1/4 A ISO 1179-2 (male) (DIN 3852)
9/16-18 UNF 2A (SAE 6) male
with 0.5 mm nozzle each
Torque value
20 Nm
(15 lb-ft)
Parts in contact with fluid
Mech. conn.: Stainless steel
Seal: FPM
Output data
Output signals
Pin 4: IO-Link interface or
freely configurable switch output
Pin 2: freely configurable switch output
Accuracy to DIN 16086,
Max. setting
≤
±0.5 % FS typ.
≤
±1.0 % FS max.
Repeatability
≤
± 0.1 % FS max.
Temperature drift
≤
± 0.03 % FS / °C max. zero point
≤
± 0.03 % FS / °C max. range
Switching outputs
Version
PNP transistor switching output
Switching current
250 mA max. each output (ohmic resistance)
Switching cycles
> 100 million
Reaction time
< 10 ms
Long term drift
≤
±0.3 % FS typ./ year
Parameterisation
Via IO-Link Interface, see chap. 9
Ambient conditions
Compensated temperature range
-25 .. +85 °C
[-13 .. +185 °F]
Operating temperature range
1)
-40 .. +85 °C / -25 .. +85 °C
[-40 .. +185 °F / -13 .. +185 °F]
Storage temperature range
-40 .. +100 °C [-40 .. +212 °F]
Medium temperature range
1)
-40 .. +125 °C / -25 .. +125 °C
[-40 .. +257 °F / -13 .. +257 °F]
- mark
EN 61000-6-1 / 2 / 3 / 4
Vibration resistance to
IEC 68-2-6 at 10..500Hz
≤
25 g
Shock resistance according to
DIN EN 60068-2-
27
(11 ms)
≤
50 g
Protection class to IEC 60529
IP 67 (M12x1 male connector, for use with IP 67 female
connector)
Other data
Supply voltage
10 .. 32 V DC
Residual ripple of supply voltage
≤
5%
Current consumption
≤
25 mA
with inactive switch outputs
≤
0.275 A
with 1 active switch output
≤
0.525 A
with 2 active switch outputs
Weight
≤
65 g