Hyco SF1/3 Скачать руководство пользователя страница 2

Expansion vessel kit

A. CONTENTS

This kit contains:

1 expansion vessel (0.5L for SF1, 2.0L for SF3)

1 check (one-way) valve

B. COMPATIBILITY

To be used in conjunction with Hyco 10L and 15L unvented (mains pressure) water

heaters.

C. WHEN THIS KIT IS REQUIRED

This kit is required if either of the following conditions applies:

1. Presence of device preventing reverse flow

If a one-way device is fitted that prevents hot water expansion, the pressure relief valve

would operate routinely on the heating cycle. This is not permissible under Water

Regulations. Note that pressure reducing valves, water meters and similar devices are

usually one-way and would block expansion.

2. Cold water off-take too close to the heater

It is a requirement that expanded heated water does not mix with drinking water

supplies. If there is a cold water off-take very close to the heater there is a risk that

the hot and cold water supplies would mix. The minimum distance required between

the heater and the nearest cold water off-take is 2.8m for the 10L and 4.2m for the

15L model.

D. INSTALLATION

Install as shown below:

IMPORTANT:ALWAYS FIT PRESSURE RELIEF VALVE SUPPLIED
WITH THE HEATER (NOT THIS KIT)

Hot

Cold

To Drain

Pressure

Relief Valve

Expansion

Vessel

Check Valve

Nearest Cold

Water Drain Off

Service Valve

Cold Water Supply

FYK0433 Expansion MAN:EYK0780 HANDYFLOW MAN  24/1/08  16:08  Page 3