SMG2000B Double Clamp Digital Phase Meter is specially designed for

measuring voltage, current and phase. It is characterized by high precision,
low price, portable hand-held and dual-channel input measuring. It’s easy to
measure the phase between U-U, I-I and U-I, identify the inductive/capacitive
circuit and the phase sequence of three-phase voltage, check the wiring group
of transformer, test the secondary circuit and busbar differential protection
system, display the phase relationship among the CT groups of a differential
protection system, and check if the wire of electric meter is correctly connected.
Under test, you do not need cut off the tested current which is inputted by
clamp-current transformer. When measuring the phase between U1 and U2,
the two input circuit loops are completely isolated, so it can completely avoid
short circuit and burning down the meter caused by misconnection. The
display of this device is high-contrast LCD screen, and the character in which
could be as high as 25mm, and can be freely rotated approximately 70 ° to
obtain the best visual effects.

The shell of the device is made of engineering insulating material,

together with a rubber anti-vibration protection casing for safety and reliability.

II. Intrinsic Error

1. Operating Conditions

1) Temperature:

23±5

)℃

2) Relative humidity:

45

75

%

3) Wave forms of measured signal: Sine wave, β=0.02
4) Frequency of measured signal: 50±0.2

Hz

5) Position of Measured current carrying conductor in clamp jaw:

Optional position

6) Amplitude range of measured signal when measuring phase: 100

220V, 0.5A

1.5A

Содержание SMG2000B

Страница 1: ...al You can find the changes in the appendix Sorry for the inconvenience If you have further questions welcome to contact with our service department The input output terminals and the test column may...

Страница 2: ...r relevant subassembly to damage In order to avoid possible danger this product can only be used within the prescribed scope Only qualified technician can carry out maintenance or repair work To avoid...

Страница 3: ...uire information about the ratings Do Not Operate without Covers Do not operate this product when covers or panels removed Use Proper Fuse Only use the fuse with type and rating specified for the prod...

Страница 4: ...Security Terms Warning indicates that death or severe personal injury may result if proper precautions are not taken Caution indicates that property damage may result if proper precautions are not tak...

Страница 5: ...s I Overview 6 II Intrinsic Error 6 III Operating Error 7 IV Other Technical Specifications 8 V Product Structure 9 VI Notes 9 VII Operation Instructions 10 VIII Adjust the display 12 IX Battery repla...

Страница 6: ...ed by clamp current transformer When measuring the phase between U1 and U2 the two input circuit loops are completely isolated so it can completely avoid short circuit and burning down the meter cause...

Страница 7: ...2 AC current see Table 2 Table 2 Error of AC current Measure range Resolution Limits of intrinsic error 200mA 0 1mA 1 0 RD 2 2A 1mA 10A 10mA 3 Phase U U U I I I see Table 3 Table 3 Error of Power fre...

Страница 8: ...ded 2 Limits of Rated Operating Error In item 1 Rated Operating Conditions the limits of rated operating error should not more than twice limits of intrinsic error IV Other Technical Specifications 1...

Страница 9: ...ce VI Notes 1 Withstand Voltage Parts between voltage input terminal and meter shell and parts between the iron core and handle of the clamp current transformer and secondary windings can withstand 10...

Страница 10: ...into jack I1 then clamp the measured circuit with clamp jaw you can measure If the measured current is less than 2A you can directly turn the switch to 2A in I1 region to obtain better measurement ac...

Страница 11: ...the voltage into U2 input the current into I1 by using measuring clamp I1 and turn the rotary switch to parameter I1U2 to measure the angle that the voltage lags the current Under measurement in the s...

Страница 12: ...nto jack I2 with measuring clamp If the phase value ranges from 0 90 then the measured load is inductive If the phase value ranges from 270 360 then the measured load is capacitive VIII Adjust the dis...

Страница 13: ...13...

Отзывы: