9
Maximum power dissipation≤ 2W
DC: 8 × 1.5V (AA, R6) Battery
AC: 220V/50Hz
6. Dimensions and weight
Dimensions: 220× 200 × 105mm
Weight: ≤ 1.4kg
III. Operation Instructions
1. Grounding resistance measurement (Fig. 1)
As Fig.1, the straight-line distance between ground
electrode E (C2, P2) and current probe C1is 40 meters. Put
potential probe P1 on the center of E, C, so that E, P, C is 20
meters away from each other and make sure potential probe P1
grounded properly.
Connect ground resistance terminals E (C2, P2), P1, C1 to