Plate frame

S100 fire damper

Mineral wool infill around

damper case

Ductwork

Concrete/masonry wall

Installation FD-2VB

S e r i e s   1 0 0   f i r e   d a m p e r   c / w   p l a t e   f r a m e   i n   m a s o n r y   w a l l

Installation FD-2VB

Approved installation method, operation and installation declaration
Page 2 of 3 - Issue B - Issued 04/03/2015

BS EN 13501-3:2005 + A1:2009

Classification report number: 301099B

Issue 1

Installation

  Aperture in masonry:

Case size + 1mm per 100mm of damper W or H.
3mm minimum.

E.G. Damper case 500mm x 200mm, aperture size 505mm x 203mm.

  All cavities to be infilled with mineral wool.

Rockwool RW5, Knauf RS100 or equivalent.

  Screw length and type to be appropriate to give secure fixing onto 

masonry.

  Screw pitch to be not more than 150mm.