background image

CVH8, HVH8, TVH8, VA9, HVA9, TVA9: APPLICATION GUIDELINE & SERVICE MANUAL

Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.

39

Accumulator

The accumulator is specifically designed to operate with R-410A

 

or

R22 respectfully; use only factory-authorized components. Under some

light  load  conditions  on  indoor  coils,  liquid  refrigerant  is  present  in

suction gas returning to compressor. The accumulator stores liquid and

allows  it  to  boil  off  into  a  vapor  so  it  can  be  safely  returned  to

compressor. Since a compressor is designed to pump refrigerant in its

gaseous state, introduction of liquid into it could cause severe damage or

total failure of compressor.

The  accumulator  is  a  passive  device  which  seldom  needs  replacing.

Occasionally  its  internal  oil  return  orifice  or  bleed  hole  may  become

plugged. Some oil is contained in refrigerant returning to compressor. It

cannot boil off in accumulator with liquid refrigerant.  The bleed hole

allows a small amount of oil and refrigerant to enter the return line where

velocity of refrigerant returns it to compressor. If bleed hole plugs, oil is

trapped in accumulator, and compressor will eventually fail from lack of

lubrication. If bleed hole is plugged, accumulator must be changed. The

accumulator has a fusible element located in the bottom end bell. (See

Fig. 42

.)  This fusible element will melt at 430

_

F//221

_

C and vent the

refrigerant if this temperature is reached either internal or external to the

system.  If fuse melts, the accumulator must be replaced.

A88410

Fig. 42 – Accumulator

To change accumulator:

1. Shut off all power to unit.
2. Recover all refrigerant from system.
3. Break vacuum with dry nitrogen. Do not exceed 5 psig.

NOTE: 

Coil  may  be  removed  for  access  to  accumulator.  Refer  to

appropriate sections of Service Manual for instructions.

4. Remove accumulator from system with tubing cutter.
5. Tape ends of open tubing.
6. Scratch  matching  marks  on  tubing  studs  and  old  accumulator.

Scratch matching marks on new accumulator. Unbraze stubs from

old accumulator and braze into new accumulator.

7. Thoroughly  rinse  any  flux  residue  from  joints  and  paint  with

corrosion-resistant coating such as zinc-rich paint.

8. Install factory authorized accumulator into system with copper slip

couplings.

9. Evacuate and charge system.

Pour  and measure  oil  quantity  (if  any)  from  old accumulator. If more

than 20 percent of oil charge is trapped in accumulator, add new POE oil

to compressor to make up for this loss. 

REFRIGERATION SYSTEM REPAIR

Leak Detection

New  installations  should  be  checked  for  leaks  prior  to  complete

charging.  If a system has lost all or most of its charge, system must be

pressurized  again  to  approximately  150  psi  minimum  and  375  psi

maximum. This can be done by adding refrigerant using normal charging

procedures or by pressurizing system with nitrogen (less expensive than

refrigerant).  Nitrogen  also  leaks  faster  than  refrigerants.    Nitrogen

cannot,  however,  be  detected  by  an  electronic  leak  detector.  (See

Fig. 43

.)

A95422

Fig. 43 – Electronic Leak Detection

Assuming  that  a  system  is  pressurized  with  either  all  refrigerant  or  a

mixture  of  nitrogen  and  refrigerant, leaks  in  the  system  can  be found

with  an  electronic  leak  detector  that  is  capable  of  detecting  specific

refrigerants.

If  system  has  been  operating  for  some  time,  first  check  for  a  leak

visually. Since refrigerant carries a small quantity of oil, traces of oil at

any joint or connection is an indication that refrigerant is leaking at that

point. 

A  simple  and  inexpensive  method  of  testing  for  leaks  is  to  use  soap

bubbles.  (See 

Fig. 44

.) Any  solution  of  water  and  soap  may  be  used.

Soap solution is applied to all joints and connections in system. A small

pinhole leak is located by tracing bubbles in soap solution around leak. If

the leak is very small, several minutes may pass  before a bubble  will

form.  Popular  commercial  leak  detection  solutions  give  better,

longer-lasting bubbles and more accurate results than plain soapy water.

The bubble solution must be removed from the tubing and fittings after

checking for leaks as some solutions may corrode the metal.

CAUTION

!

PERSONAL INJURY HAZARD

Failure to follow this caution may result in personal injury.
Wear  safety  glasses,  protective  clothing,  and  gloves  when  handling

refrigerant.

WARNING

!

ELECTRICAL SHOCK HAZARD

Failure to follow this warning could result in personal injury or death.

Before  installing,  modifying,  or  servicing  system,  main  electrical

disconnect switch must be in the OFF position. There may be more than

1 disconnect switch. Lock out and tag switch with a suitable warning

label. 

WARNING

!

PERSONAL INJURY AND UNIT DAMAGE  HAZARD

Failure to follow this warning could result in personal injury or death.

Due to the high pressure of nitrogen, it should never be used without a

pressure regulator on the tank.

BEEP

BEEP

Содержание CVH8

Страница 1: ...safety glasses protective clothing and work gloves Use quenching cloth for brazing operations Have fire extinguisher available Read these instructions thoroughly and follow all warnings or cautions in...

Страница 2: ...7 8 9 10 11 12 Example Part Number V A 9 24 G K A 1 0 0 Brand V Variable Speed KEY CHARACTERISTIC A Air Conditioner H Heat Pump TYPE 6 16 SEER 7 17 SEER 8 18 SEER 9 19 SEER NOMINAL EFFICIENCY 24 24 00...

Страница 3: ...t of comfort with the convenience of fingertip trouble shooting and diagnostic capability These units can also use a standard 2 stage or single stage thermostat for limited functionality ELECTRICAL Ta...

Страница 4: ...field electrical connections for tightness This should also be done after unit has reached operating temperatures especially if aluminum conductors are used Unit Electrical Power Power wires from the...

Страница 5: ...h cooling and dehumidification As the building load increases the motor will increase speed until it is at maximum speed at the maximum building load At unit start up there is a slight delay and thrus...

Страница 6: ...ommunication The green LED will be turned off when using a standard 2 stage non communicating heat pump thermostat Amber Status Light Amber colored STATUS light indicates operation and error status Se...

Страница 7: ...80ft 24 4 m or less allow system to operate in cooling mode at least 25 minutes If conditions are favorable check system charge by subcooling method If any adjustment is necessary adjust charge slowly...

Страница 8: ...n Cooling Mode CVH8 HVH8 TVH848 A200333 Fig 14 Charging in Cooling Mode CVH8 HVH8 TVH860 Table 5 Required Charge Adjustment for Indoor Coil Model AC Furnace Coil or Fan Coil Model 24 25 36 37 48 49 60...

Страница 9: ...echarge refer to the unit rating plate and indoor fan coil furnace coil per Table 4 and Table 5 for additional charge needed Refrigerant charge adjustment amount for adding or removing 0 6 oz ft 17 74...

Страница 10: ...tify the type and size of unit to the control On new units the model and serial numbers are inputted into the AOC board s memory at the factory If a model plug is lost or missing at initial installati...

Страница 11: ...alant before the cap is reinstalled The factory RTV can be reused as long as none of it has been removed during the cap removal 8 Reinstall compressor sound blanket making sure discharge thermistor an...

Страница 12: ...stage occurs suction pressure is checked at each stage in between current and demanded stage This is to prevent ramping of compressor speed too quickly and creating a low pressure situation As long as...

Страница 13: ...istor comparisons are not performed during low ambient cooling or defrost operation Failed Thermistor Default Operation Factory defaults have been provided in the event of failure of outdoor air therm...

Страница 14: ...d Damaged Model Plug Check model plug for corrosion or breakage replace if necessary Check Model Plug resistance per the wiring diagram Model Plug not fully engaged on board Align per the silkscreen l...

Страница 15: ...ity see resistance chart to check resistance at given temperature Broken or Damaged Sensor Check harness for continuity see resistance chart to check resistance at given temperature Hardware damage to...

Страница 16: ...eading to gage reading at service valve see transducer measurement chart Check system for electrical shorts and correct replace transducer Heat damage during brazing Compare transducer reading to gage...

Страница 17: ...STAGE 2 WARMUP DELAY 10 Minutes Both High voltage power cycle No action 69 System Malfunction INVERTER COMPRESS OR INTERNAL FAULT Elevates to this fault code after 5 hidden occurrences of itself 15 M...

Страница 18: ...ow too low or off Troubleshoot outdoor fan motor and make sure it is working Reversing Valve Bypass or Reversing Valve not energized Reversing Valve stuck halfway Ensure AOC fuse is good 24 VDC in coo...

Страница 19: ...Incoming power supply voltage Check voltage versus unit rating plate for allowable range Loose or incorrect wire connections Check incoming power leads and leads to the compressor plug 79 Local COMPR...

Страница 20: ...ction Cool Restriction in Circuits or Tubing Repair restriction Heat EXV Malfunction Troubleshoot EXV see guide below Heat Service Valve left closed Liquid Service Valve Ensure Liquid Service Valve is...

Страница 21: ...ndoor coil or filter for restriction debris and clean if necessary Heat Furnace plus Heat pump application Furnace stuck on If not in Defrost and Furnace is running same time as heat pump troubleshoot...

Страница 22: ...ent heating or high ambient cooling Over charge Check system charge Inverter damage Replace inverter 91 Local INVERTER VDC OUT OVER VOLTAGE EVENT Elevates to fault code 97 after 5 occurrences 5 Minute...

Страница 23: ...rter will reduce speed to a lower stage Both Refer to fault code 99 99 System Malfunction HIGH TORQUE LOCKOUT Elevated from fault code 98 when 98 occurs at lowest stage 2 hours Cool Overcharged System...

Страница 24: ...olt connection status OK between AOC and MOC Off No Power Table 12 AOC LED Descriptions Sizes 25 36 37 48 49 AND 60 Reference Color Status Description STATUS Amber Steady On AOC status standby mode Bl...

Страница 25: ...Table 16 AOC LED Descriptions Size 24 Reference Color Status Condition Description STATUS Amber Steady On Normal AOC status standby mode Blinking Abnormal AOC function fault status COMM Green Steady...

Страница 26: ...res securing the compressor power harness to the control box Remove compressor power harness from control box Replace wire tie with supplied wire tie do not fasten at this time The second wire tie for...

Страница 27: ...pushing one side down then the other NOTE DO NOT SCRAP SEALANT A210665 13 Reinstall compressor sound blanket making sure discharge thermistor and compressor power harness are routed as they were from...

Страница 28: ...and Black 8 Disconnect fan motor power harness plug 9 Disconnect reversing valve PEV plug See Figure Below 10 Disconnect high pressure switch plug 11 Disconnect EXV plug 12 Disconnect suction pressure...

Страница 29: ...MANUAL Manufacturer reserves the right to change at any time specifications and designs without notice and without obligations 29 A210667 Fig 32 Compressor and Fan Harness Unit sizes 25 36 37 48 49 an...

Страница 30: ...E MANUAL Manufacturer reserves the right to change at any time specifications and designs without notice and without obligations 30 A210669 Fig 34 Wire Harness Connections Unit sizes 25 36 37 48 49 an...

Страница 31: ...control box Replace wire tie with one supplied do not fasten at this time The second wire tie for the choke on the compressor is supplied with new harness on the replacement compressor highlighted wi...

Страница 32: ...that terminal cover remain installed during compressor installation 15 Using caution and the appropriate lifting device place replacement compressor in unit and secure with appropriate mounting hardw...

Страница 33: ...icates clean system 28 Check system for normal operation If unit is a heat pump switch from heating to cooling a few times to verify component operation Severe Burnout Perform steps 1 22 as specified...

Страница 34: ...VICE MANUAL Manufacturer reserves the right to change at any time specifications and designs without notice and without obligations 34 WIRING DIAGRAMS VA9 A160127 Fig 36 VA9 WIRING DIAGRAM Size 24 A16...

Страница 35: ...ICE MANUAL Manufacturer reserves the right to change at any time specifications and designs without notice and without obligations 35 WIRING DIAGRAMS VH8 A160129 Fig 38 VH8 WIRING DIAGRAM Size 24 A160...

Страница 36: ...still hot 2 Silver brazing alloy is used on copper to brass copper to steel or copper to copper Flux is required when using silver brazing alloy Do not use low temperature solder 3 Fluxes should be u...

Страница 37: ...at completion of the procedure Attach recovery system or vacuum pump to gauge set as needed for the service procedure The service valves must be open to evacuate the unit through the line set service...

Страница 38: ...ave a bleed port Therefore minimal equalization takes place after shutdown TXVs are specifically designed to operate with R 410A or R 22 refrigerant use only factory authorized TXV s Do not interchang...

Страница 39: ...em Pour and measure oil quantity if any from old accumulator If more than 20 percent of oil charge is trapped in accumulator add new POE oil to compressor to make up for this loss REFRIGERATION SYSTEM...

Страница 40: ...replace liquid line filter drier evacuate system and recharge with correct refrigerant quantity Coil Removal Coils are easy to remove if required for compressor removal or to replace coil 1 Shut off...

Отзывы: