HVAC Partners EHC09AKCN Скачать руководство пользователя страница 3

482 01 2231 02

3

Specifications are subject  to change without notice

ATTACH FUSE BOX OR CIRCUIT BREAKER BOX

1. For 15kW and 20kW fused models:

After installing heater assembly, attach fuse assembly to side of

fan coil unit by inserting fuse box tab between insulation and to

left side of unit and fan deck. Mount front of assembly to side

flange with two (2) screws provided. On fan coil units size 4200

and larger, remove wire tie that shortens wire length between

heater and fuses. Fuse cover is closed by engaging dimples in

fuse box. (See Figure 2)

2. For 24kW and 30kW fused models:

Fuse assembly is mounted on heater. Be sure fuse cover is

closed by engaging clip latch on unit top panel. (See Figure 1)

ELECTRICAL SHOCK.
Failure to follow this warning could result in death and/or

personal injury.
Close fuse box before power is turned to ON position.

!

WARNING

3. For 5kW through 20kW circuit breaker models:

After installing heater assembly, attach circuit breaker assembly

to unit with screws provided. (See Figure. 3) On fan coil units

size 4200 and larger, remove wire tie that shortens wire length

between heater and circuit breaker assembly to allow mounting

of circuit breaker assembly. (See Figure 3)

4. Circuit breaker models require installing a bezel in unit door to

provide safe access to circuit breakers. Bezel mounts on inside

of blower door. (See Figure 4)

Figure 2

Fused Model Installation

a. Cut insulation away from access hole in blower access panel.

Slide bezel flanges under insulation. Lip on bezel must protrude

inward toward unit.

b. Secure bezel to panel with two (2) No. 6 hex head screws. Insert

screws through original cover plate holes on access panel and

drive into engagement holes on bezel flanges.

ELECTRICAL CONNECTIONS

Refer to unit instructions for recommended wiring procedures.

Install wiring in accordance with all applicable local and national

codes.

Connect heater wiring harness plug to receptacle on fan control

board or wire harness. A positive connection must be made

between plug and receptacle. Plug will interlock with receptacle

when properly seated. Harness contains both 24V control and

high

voltage wiring. Blower power is provided through heater

harness.

NOTE: 

Units with or without electric heaters require a minimum

CFM. Refer to unit wiring label to ensure the fan speed selected with

electric heaters is equal to or greater than the minimum fan speed

indicated. The minimum CFM for cooling is determined by the

outdoor unit requirements. Use the higher of the two for year

round

operation.

Figure 3

Circuit Breaker Model Installation

A. Wire 24V Control Systems

1. Connections to unit

Use No. 18 AWG color

coded, insulated (35 Deg. C minimum)

wire to make low

voltage connections between thermostat, fan

coil unit, and outdoor unit. If thermostat is located more than 100

ft. from unit (as measured along the low

voltage wire), use No.

16 AWG color

coded, insulated (35 Deg. C minimum) wire. All

wiring must be separated from line voltage power leads. Refer

to outdoor unit wiring instructions for additional wiring procedure

recommendations.

2. Transformer

Transformer is factory wired for 230V operation. For 208V ap-

plications, disconnect black wire on transformer 230V terminal

and reconnect it to 208V terminal. (See Figure 5) The secondary

circuit of transformer is protected by a 5

amp fuse mounted on

fan control board.

3. Heater staging

The units are shipped circuited for single stage operation and

the Observer Wall Control only supports single stage operation.

4. Rectifier and Time Delay Boards

Each heater element is controlled by a relay mounted on the

heater panel. The relay has a 24V DC coil. Each relay has a

small rectifier board attached directly to relay coil terminals. The

rectifier board converts incoming 24V AC control signal to DC.

Some heaters may have up to three relays. These relays are for

future use with a control capable of staging the electric heat. The

second and/or third relay rectifier board also has a time delay

feature and a small jumper wire built into it. With the jumper un-

cut, the time delay allows the second stage heat to be energized

approximately five (5) seconds after the first stage. On 24kW,

Содержание EHC09AKCN

Страница 1: ... local codes with National Electrical Code ANSI NFPA 70 1996 or current edition The information contained in this manual is intended for use by a qualified service technician familiar with safety procedures and equipped with the proper tools and test instruments Shut OFF electric power at unit disconnect and or service panel before beginning the following proce dures WARNING USE EHC heater kits ar...

Страница 2: ...ters and certified single point wiring kit 15kW 20kW are not recommended for specific heat pump applications see AIRFLOW DELIVERY CFM HEAT PUMP MINIMUM CFM WHEN USING ELECTRIC HEAT CFM FCM Model Size Outdoor Unit Size Heater Size kW 9 15 20 24 30 24 18 625 24 725 875 30 875 875 1040 36 970 970 1040 36 24 875 30 875 1100 1150 36 975 1100 1225 42 1125 1125 1225 48 30 875 875 1150 36 975 1100 1225 42...

Страница 3: ...on must be made between plug and receptacle Plug will interlock with receptacle when properly seated Harness contains both 24V control and high voltage wiring Blower power is provided through heater harness NOTE Units with or without electric heaters require a minimum CFM Refer to unit wiring label to ensure the fan speed selected with electric heaters is equal to or greater than the minimum fan s...

Страница 4: ...nterrupted or unbroken ground to minimize personal injury if an electrical fault should occur The ground may consist of electrical wire or metal conduit when installed in accordance with existing electrical codes See Ground Conduit Note below WARNING NOTE Use UL listed conduit and conduit connector for connecting supply wire s to unit to obtain proper grounding If conduit connection uses reducing ...

Страница 5: ...notice Figure 5 Connection of Transformer 230 C 208 BRN RED YEL BLK SECONDARY PRIMARY A94067 Figure 6 9 kW Non fused Heaters Figure 7 15 and 20 kW Fused Heaters Figure 8 15 and 20 kW Circuit Breakers Figure 9 lug 15 kW 3 Phase Heater Figure 10 24 and 30 kW Heaters ...

Страница 6: ...01 2231 02 6 Specifications are subject to change without notice Figure 11 24 and 30 kW Heaters Figure 12 24 and 30 kW Heaters Figure 13 Conversion of Circuit Breaker Figure 14 Heater Rating Label Location ...

Страница 7: ...3 24 18 0 3 Fuse 50 1 55 4 71 2 77 8 4 4 8 8 80 80 94 95 24 18 0 1 Fuse 86 7 95 5 116 9 127 9 1 1 6 6 125 150 115 116 EHC30AHCF3 30 22 5 3 Fuse 62 6 69 2 86 8 95 0 3 3 8 8 90 100 97 98 30 22 5 1 Fuse 109 0 120 0 144 8 158 5 0 00 6 6 150 175 117 150 FIELD MULTIPOINT WIRING OR 24 AND 30 KW SINGLE PHASE Heater Model Heater kW P H A S E Heater Amps 208 230V Minimum Circuit Ampacity 208 230V k Minimum ...

Страница 8: ...482 01 2231 02 8 Specifications are subject to change without notice WIRING DIAGRAM FOR HEAT ACCESSORIES EHC09AKCN Field Convertible to three phase N NON FUSED EHC15AKF B F FUSED B CIRCUIT BREAKER ...

Страница 9: ...482 01 2231 02 9 Specifications are subject to change without notice WIRING DIAGRAM FOR HEAT ACCESSORIES EHC20AKF B F FUSED B CIRCUIT BREAKER EHC25AHCF EHC30AHCF Shipped three phase see below F FUSED ...

Страница 10: ...cations are subject to change without notice WIRING DIAGRAM FOR HEAT ACCESSORIES EHC25AHCF EHC30AHCF Field Converted to single phase see below F FUSED Copyright 2015 International Comfort Products Lewisburg Tennessee 37091 USA ...

Отзывы: