Page 9 

in the liquid line after the condenser and just 
ahead of the filter-drier.  It has sweat connec-
tions, and is in a horizontal position.  The 
manufacturer may label the receiver as a muf-
fler or a drier but it is, in fact, an empty shell. 
 
CRANKCASE PRESSURE REGULATOR - 
 
 

The USL-2 with R404a refrigerant em-

ploys a crankcase pressure regulator in the 
suction line.  The CPR is set for 12 psi.  The 
purpose of the valve is to maintain a low suc-
tion pressure on start-up so that the compres-
sor will start properly.  On start-up, the valve 
will hold the suction pressure at the desired 
setting until the suction pressure has dropped 
below the setting, then the valve will open. 
 
 

If it becomes necessary to check or reset 

the setting, the case must be warm such as af-
ter a defrost cycle or from an initial  warm 
case condition.  Put a suction compound gauge 
on the compressor suction valve, start the com-
pressor.  If the pressure needs to be reduced 
turn the adjustment screw clockwise or, coun-
terclockwise to raise the pressure.  DO NOT 
SET THE VALVE BASED ON THE NAME-
PLATE AMPERAGE RATING AS THE 
PRESSURE SETTING WILL BE TOO HIGH 
AND THE COMPRESSOR WILL NOT 
START PROPERLY. 
 
 
  

 

Содержание USL-2

Страница 1: ...URE Solid Door Reach In for Ice Cream and Frozen Foods P N OII USL January 2006 First Call for help US and Canada 1 800 922 1919 Soporte T cnico y Asistencia M xico 01 800 522 1900 For a Service Netwo...

Страница 2: ...apacities 4 General Upkeep Care and Cleaning Routine Maintenance 4 Power Switches Temperature Control 5 Thermometer Electrical Enclosure 5 Defrost Time Clock 6 Defrost Heater Thermostat and Replacemen...

Страница 3: ...xi mum operating efficiency INSTALLATION and START UP SKID The skid should be left on the cabinet until it is near the final location The skid pro vides protection for both the case and floor The skid...

Страница 4: ...for durability and ease of cleaning Care should be taken when loading the shelves with product Product on the highest level of shelves should not touch the evapora tor drain pan This pan gets warm du...

Страница 5: ...ps Size Wt USL 2 15 0 20 amp 875 BTU CAPACITIES Rating Temps F BTU HR Evap Cond Amb USL 2 2280 20 110 90 During June 95 R404A refrigerant was phased into use on the USL 2 The refriger ant charge is 46...

Страница 6: ...obably need resetting to reflect the proper case temperature Using a separate thermometer located on a shelf in the case compare this temperature to that on the case thermometer If the case thermomete...

Страница 7: ...lowest usage Defrost is time initiated and tempera ture terminated If the thermostat should fail the timer is equipped with a failsafe set at 40 minutes that will allow defrost to terminate on time DE...

Страница 8: ...rature Adjust the expansion valve as follows 1 Attach two sensing probes to the evapora tor one under the clamp holding the ex pansion valve sensing bulb and the other securely taped to one of the ret...

Страница 9: ...g to the fol lowing procedure 1 Discharge the refrigerant nitrogen mixture allowing it to blow from the system as rapidly as possible into an empty cylinder Be sure that all service valves and solenoi...

Страница 10: ...pres sor will start properly On start up the valve will hold the suction pressure at the desired setting until the suction pressure has dropped below the setting then the valve will open If it becomes...

Страница 11: ...e air flow restriction 3 Defective condenser fan mo tor 3 Replace 4 Air or non condensable gas ses in system 4 Leak check change drier evacuate and recharge Warm storage temperatures 1 Temperature con...

Страница 12: ...temperature con trol 4 Replace 5 Power disconnected 5 Check service cord or wir ing connections Compressor will not start cuts out on overload 1 Low voltage 1 Contact electrician 2 Defective compress...

Страница 13: ...nd R404 KAAB 007E CAA Condenser Fan Motor EMS ESPL25EM1 Evaporator Fan Motor Morrill SPB5EM1 Light Ballast 8G3738W Incandescent Lamp GE 40A15 WARRANTY AND PARTS INFORMATION Please read carefully to as...

Страница 14: ...s will not be shipped from the Hussmann factory They may be obtained from your nearest Copeland Wholesaler Your wholesaler will replace free of charge any compressor found to be defective within twelv...

Страница 15: ......

Отзывы: