IGIP-DSI-03, DSRPI-03 & DSI03-Y, DSRPI-03Y-0508

6

Plumbing

Waste Outlet and P-TRAP

The waste outlet is located off the center of the case on 

one side allowing drip piping to be run lengthwise under 

the fixture.

A 1-1/” P-TRAP and threaded adapter are supplied with 

each fixture. The P-TRAP must be installed to prevent air 

leakage and insect entrance into the fixture.

NOTE:   PvC-DWv solvent cement is recommended. Follow the 

manufacturer’s instructions.

Access Panels

All electrical and drain access panels are clearly labeled on 

the deck of the produce stand. The access for condensing 

units (in the self contained units) is located on the side of 

the stand, at the end. Ends of stand are fitted for removal, 

if condensing unit has to be taken out.

Installing Condensate Drain

Poorly  or  improperly  installed  condensate  drains  can 

seriously interfere with the operation of this refrigerator, and 

result in costly maintenance and product losses. Please 

follow the recommendations listed below when installing 

condensate drains to insure a proper installation:

1.   Never use pipe for condensate drains smaller 

than the nominal diameter of the pipe or P-TRAP 

supplied with the case.

.   When connecting condensate drains, the P-TRAP 

must be used as part of the condensate drain 

to prevent air leakage or insect entrance. Store 

plumbing system floor drains should be at least 14” 

off the center of the case to allow use of the P-TRAP 

pipe section. Never use two water seals in series in 

any one line. Double P-TRAPS in series will cause a 

lock and prevent draining.

3.   Always provide as much down hill slope (“fall”) as 

possible; 1/8” per foot is the preferred minimum. 

PVC pipe, when used, must be supported to 

maintain the 1/8” pitch and to prevent warping.

4.   Avoid long runs of condensate drains. Long runs 

make it impossible to provide the “fall” necessary for 

good drainage.

5.   Provide a suitable air break between the flood rim of 

the floor drain and outlet of condensate drain. 1” is 

ideal.

6.   Prevent condensate drains from freezing:

a. Do not install condensate drains in contact with 

non-insulated suction lines. Suction lines should 

be insulated with a non absorbent insulation 

material such as Armstrong’s Armaflex.

b. Where condensate drains are located in dead 

air spaces (between refrigerators or between a 

refrigerator and a wall), provide means to prevent 

freezing. The water seal should be insulated to 

prevent condensation.

Hose Reel

If an optional hose reel is ordered, it will be installed at the 

factory. The water supply valve is located next to the access 

panel. Connect the water supply to the valve.

Spray Hose

If an optional quick-disconnect spray hose is ordered, a 

pressure regulating valve should be installed. If the water 

pressure exceeds 45 PSI, the valve should be set for 30 

to 35 PSI outlet pressure.

Refrigeration

Refrigerant Type

The  standard  refrigerant  will  be  R-  unless  otherwise 

specified on the customer order. Check the serial plate on 

the case for information.

Piping

The  refrigerant  line  outlets  are  located  under  the  case. 

Locate first the electrical box, the outlets are then on the 

same side of the case but at the opposite end. Insulate 

suction lines to prevent condensation drippage.

Access Panels

All electrical and drain access panels are clearly labeled on 

the deck of the produce stand. The access for condensing 

units (in the self contained units) is located on the side of 

the stand, at the end. Ends of stand are fitted for removal, 

if condensing unit has to be taken out.

Refrigeration Lines

Liquid 

Suction

3/8” O.D.

5/8” O.D. 

NOTE:   The standard coil is piped at 

5

/

8

” (suction); however, 

the store tie-in may vary depending on the number of 

coils and the draw the case has. Depending on the case 

setup, the connecting point in the store may be 

5

/

8

”, 

7

/

8

”, 

or 1

1

/

8

”. Refer to the particular case you are hooking up.

Refrigerant  lines  should  be  sized  as  shown  on  the 

refrigeration legend furnished by the store.
Install 

P-TRAPS

 (oil traps) at the base of all suction line 

vertical risers.

Pressure drop

 can rob the system of capacity. To keep the 

pressure drop to a minimum, keep refrigerant line run as 

short as possible, using the minimum number of elbows. 

Where elbows are required, use long radius elbows only.

Control Settings

See DSI-03, DSRPI-03 & DSI03-Y, DSRPI-03Y technical 

data sheet for the appropriate settings for your merchandiser. 

Maintain  these  parameters  to  achieve  near  constant 

product  temperatures.  Product  temperature  should  be 

measured  first  thing  in  the  morning,  after  having  been 

refrigerated  overnight.  For  all  multiplexing,  defrost 

should  be  time  terminated.  Loadmaster  valves  are  not 

recommended.  Defrost  times  should  be  as  directed  in 

the DSI-03, DSRPI-03 & DSI03-Y, DSRPI-03Y technical 

data sheet. The number of defrosts per day should never 

change. The duration of the defrost cycle may be adjusted 

to meet conditions present at your location.

Содержание Specialty Products DSI-03

Страница 1: ...PI 03 DSI03 Y DSRPI 03Y ISLAND PRODUCE p n IGIP DSI 03 DSRPI 03 DSI03 Y DSRPI 03Y 0508 INSTALLATION OPERATION GUIDE CHINO DSI 03 DSRPI 03 DSIO3 Y DSRPI 03Y ISLAND PRODUCE Rev 0508 Installation Operati...

Страница 2: ...s Information on DSI 03 DSRPI 03 DSI03 Y DSRPI 03Y Island Produce Cases Shipping Damage All equipment should be thoroughly examined for shipping damage before and during unloading This equipment has b...

Страница 3: ...DSRPI 03Y Impact Plan View Scale 1 8 DSRPI 03 Shelf Rack Option Scale 3 8 DSRPI 03 DSRPI 03Y Impact Standard Section Scale 3 8 DSI 03 DSI 03Y Impact Standard Section Scale 3 8 Vision 16 9 3 8 Drain O...

Страница 4: ...as close to its permanent position as possible Remove the top of the crate Detach the walls from each other and remove from the skid Unbolt the case from the skid The fixture can now be lifted off the...

Страница 5: ...ty to install case s according to local construction and health codes 6 Slide second case up to first case snugly Then level second case to the first case so glass front bumper and top are flush 7 App...

Страница 6: ...to prevent freezing The water seal should be insulated to prevent condensation Hose Reel If an optional hose reel is ordered it will be installed at the factory The water supply valve is located next...

Страница 7: ...rator outlet 2 From a refrigerant pressure temperature chart determine the saturation temperature at the observed suction pressure 3 Measure the temperature of the suction gas at the thermostatic remo...

Страница 8: ...the air in and around the case area free of foreign gasses and fumes or food will rapidly deteriorate 3 Maintain the display merchandisers temperature controls as outlined in the refrigerator section...

Страница 9: ...orescent Lamps Fluorescent lamps are furnished with a shatterproof protective coating The same type of lamp with protective coating must be used if replaced This lamp has been treated to resist breaka...

Страница 10: ...trol is working properly and that no outside doors or windows are open allowing moisture to enter store FOR PROMPT SERVICE When contacting the factory be sure to have the Case Model and Serial Number...

Страница 11: ...21 00 Refrigerated Island Produce Stand W0900006 DSRP 18 Remote Evaporator w Fan Motors Liquid Solenoid opional T Stat optional Tx Valve optional 15V 3 6A Labeled Controller MOTOR S Computer Case Cont...

Страница 12: ...L1 N L 125 02 0030 2 125 03 1077 2 125 02 0031 3 125 03 1080 FIXTURE LITHONIA FIXTURE LITHONIA FIXTURE LITHONIA FIXTURE LITHONIA FIXTURE LITHONIA FIXTURE LITHONIA FIXTURE LITHONIA FIXTURE LITHONIA FI...

Страница 13: ...1 50 60 Hz L1 L2 L3 N G L LIGHT SWITCH TIPPETTE 125 01 0311 CIRCUIT 1 BLUE BLUE YELLOW YELLOW RED RED BALLAST 125 01 3278 B228PUNV C F35T5 60 125 03 1135 F35T5 60 125 03 1135 LIGHT SWITCH 125 01 8509...

Страница 14: ...208 240 VAC 60 Hz SWITCH 125 01 0271 BUNDLE BLUE THERMOSTAT 225 01 2010 T X 4 N 3 1 2 DEFROST TIMER PARAGON 8045 20 208 V 60 Hz 125 01 0715 PRESSURE SAFETY 225 01 0706B COND FAN 208 VAC BUNDLE BROWN...

Страница 15: ...3 125 03 0012B 125 02 0020 4 125 03 0037A 4 M M M M M FIXTURE LITHONIA FIXTURE LITHONIA FIXTURE LITHONIA FIXTURE LITHONIA FIXTURE LITHONIA FIXTURE LITHONIA FIXTURE LITHONIA L1 N 120 VAC 60 Hz MCA 3 2...

Страница 16: ...03 0037A 4 M M M M M M M M FIXTURE LITHONIA FIXTURE LITHONIA FIXTURE LITHONIA FIXTURE LITHONIA FIXTURE LITHONIA FIXTURE LITHONIA FIXTURE LITHONIA FIXTURE LITHONIA BUNDLE ORANGE L1 N 120 VAC 60 Hz MCA...

Страница 17: ...AGE OF 1 1 9 6 07 Northgate 18 W0900025 DSRPI 03 6x12 BUNDLE BROWN 120 VAC 1 60 Hz M M BLK 14 WHITE 14 EVAP FAN MOTORS 2 GE 9W CW W 125 01 0614 9W 33A 120VAC L1 N MCA 74A MOP 15A BUNDLE BROWN 120 VAC...

Страница 18: ...16 663363 CIRCUIT 1 NOTE CASE MUST BE GROUNDED 12 7 10 9 12 7 10 9 L1 L2 208 V 240 V LOADING CONDENSING UNIT COPELAND FJAM A200 CFV 020 1H10402500 DEFROST TIMER PARAGON 8045 20 208 V 60 Hz 125 01 0715...

Страница 19: ...er should perform a complete start up evaluation prior to the loading of food into the refrigerator which includes such items as a Initial temperature performance Coils should be properly fed with a r...

Страница 20: ...loaded with warm product 2 Is the product loaded beyond the Safe Load Line markers 3 Are the return air ducts blocked 4 Are the entering air ducts blocked 5 Is a dumped display causing turbulent air f...

Страница 21: ...ure recovery Food store refrigerators are not food chillers nor can they reclaim quality lost through previous mishandling d Care must be taken when cross merchandising products to ensure that potenti...

Страница 22: ...__________________ _______________ ___________________________________________________________________________________________________ _______________ _________________________________________________...

Отзывы: