3-4
S
TART UP
/ O
PERATION
P/N 0515388_E
U.S. & Canada 1-800-922-1919 • Mexico 01 800-890-2900 • www.hussmann.com
TEMPERATURE ADJUSTMENT
Rotate the adjustment knob counter clockwise
for a warmer setpoint or clockwise for a colder
setpoint.
• While the temperature is being adjusted,
the optional display shows the setpoint (cut
out value). A few seconds after the temper-
ature is set, the display reverts to showing
the sensed temperature in the merchandiser.
ALARMS AND CODES
F
LASHING
T
EMPERATURE OR
S
ENSOR
A
LARM
LED, E1
OR
E2
If the Temperature or Sensor Alarm LED
(red) on the controller and display is flashing,
a temperature sensor has failed. The display
shows E1 if the case sensor has failed or E2 if
the evaporator sensor has failed.
If the merchandiser sensor fails, refrigeration
will run continuously. Turn off, or repeat a
duty cycle of a few minutes on and a few
minutes off.
DEFROST TERMINATION SWITCH
Merchandisers may use a defrost termination
switch, instead of an evaporator sensor to
terminate a defrost cycle. The defrost
termination switch is temperature activated
and senses the completion of defrost.
MANUAL DEFROST
Note:
This procedure initiates
a manual or forced
defrost.
IMPORTANT:
Return the control knob to its
original setting (Step 1) once the manual
defrost has been initiated.