Defrost Sensor (0=time, 1=S5. 2=S4)
d10
0
2
0
0
Pump down delay
d16
0 min
60 min
0 min
0 min
Drain delay
d17
0 min
60 min
0 min
0 min
Max. aggregate refrigeration time between two
defrosts
d18 0 hours 48 hours 0 hours
Defrost on demand - S5 temperature's permitted
variation during frost build-up. On central plant choose
20 K (=off )
d19
0.0 K
20.0 k
20.0 K
Delay of hot gas defrost
d23
0 min
60 min
0 min
0 min
Fan
Fan stop at cutout compressor
F01
no
yes
no
no
Delay of fan stop
F02
0 min
30 min
0 min
0 min
Fan stop temperature (S5)
F04 -50.0°C 50.0°C
50.0°C
50.0°C
HACCP
Actual temperature measurement for the HACCP
h01
Last registered peak temperature
h10
Selection of function and sensor for the HACCP
HACCP function. 1 = S4 used (maybe also S3). 2 = S5
h11
0
2
0
0
Alarm limit for the HACCP function
h12 -50.0°C 50.0°C
8.0°C
8.0°C
Time delay for the HACCP alarm
h13
0 min. 240 min. 30 min.
30 min.
Select signal for the HACCP function. S4% (100% = S4,
h14
0%
100%
100%
100%
Real time clock
Six start times for defrost.
Setting of hours.
0=OFF
t01- 0 hours 23 hours 0 hours
0 hours
Six start times for defrost.
Setting of minutes.
0=OFF
t11-
0 min
59 min
0 min
0 min
Clock - Setting of hours
t07 0 hours 23 hours 0 hours
0 hours
Clock - Setting of minute
t08
0 min
59 min
0 min
0 min
Clock - Setting of date
t45
1
31
1
1
Clock - Setting of month
t46
1
12
1
1
Clock - Setting of year
t47
0
99
0
0
Miscellaneous
Delay of output signals after start-up
o01
0 s
600 s
5 s
5 s
Input signal on DI1. Function:
o02
1
11
0
0
Network address
o03
0
240
0
0
On/Off switch (Service Pin message)
o04
OFF
ON
OFF
OFF
Access code 1 (all settings)
o05
0
100
0
0
Used sensor type (Pt /PTC/NTC)
o06
Pt
ntc
Pt
Pt
Display step = 0.5 (normal 0.1 at Pt sensor)
o15
no
yes
no
no
Max hold time after coordinated defrost
o16
0 min
60 min
20
20
Select signal for display view. S4% (100%=S4, 0%=S3) o17
0%
100%
100%
100%
Input signal on DI2. Function:
o37
0
12
0
0
Configuration of light function (relay 4)
o38
1
3
1
1
Activation of light relay (only if o38=2)
o39
OFF
ON
OFF
OFF
Rail heat On time during day operations
o41
0%
100%
100
100
Rail heat On time during night operations
o42
0%
100%
100
100
Rail heat period time (On time + Off time)
o43
6 min
60 min 10 min
10 min
Case cleaning. 0=no case cleaning. 1=Fans only. 2=All
o46
0
2
0
0
Selection of EL diagram. See overview page 6
o61
1
10
1
1
33
Содержание Q1-SSN
Страница 11: ...Spec Sheet 11...
Страница 19: ...Wiring Diagrams 19...
Страница 20: ...Wiring Diagrams Cont d 20...
Страница 21: ...Wiring Diagrams Cont d 21...
Страница 22: ...Wiring Diagrams Cont d 22...
Страница 23: ...Wiring Diagrams Cont d 23...
Страница 24: ...Wiring Diagrams Cont d 24...
Страница 25: ...Wiring Diagrams Cont d 25...
Страница 26: ...Wiring Diagrams Cont d 26...
Страница 27: ...Wiring Diagrams Cont d 27...
Страница 28: ...Wiring Diagrams Cont d 28...
Страница 35: ...Controller for temperature control AK CC 210 User Guide ADAP KOOL Refrigeration control systems 35...