background image

P/N 0404844A

3 of 6

HUSSMANN CORPORATION, Bridgeton, MO 63044-2483 U.S.A.

5

/

(142)

FAN

M5NGE

38

(966)

30

(762)

1

/

2

(190)

53 

5

/

8

(1363)

24 

1

/

4

(617)

16

(406)

14

(356)

42 

1

/

4

(1074)

18 

1

/

8

(461)

C

O

I

L

1

/

4

(234)

3

/

8

(111)

27

 

(686)

27 

1

/

(699)

29 

1

/

(748)

33

 7

/

(861)

40 

5

/

(1031)

77 

7

/

8

(1978)

Refrigeration Outlet

18 

1

/

8

(461)

REFRIGERATION DATA

Note:

This data is based on store

temperature and humidity that does not
exceed 75°F and 55% R.H.

M5NE

Discharge Air °F

29

Evaporator °F

21

Unit Sizing °F

19

Btu/hr/ft**

M5NE

Parallel

1470

Conventional

1575

**For all refrigeration equipment other than
Husssmann, use conventional BTU values.

DEFROST DATA

M5NE

Frequency (hr)

6

Defrost Water (lb/ft/day)

9

(±15% based on case configuration and
product loading.

O

FFTIME

M5NE

Temp Term °F

48°F

Failsafe Minutes

30

E

LECTRIC OR

G

AS

Not Recommended

Standard Defrost Thermostat

Close on rise: close 48°F – open 33°F

CONVENTIONALCONTROLS

Low Pressure Backup Control
CI/CO**

14/4°F

Indoor Unit Only, Pressure Defrost
Termination**

48°F

**Use a Temperature Pressure Chart to
determine PSIG conversions.

PHYSICAL DATA

M5NE

Drip Pipe (in.)

1

/

2

Liquid Line (in.)

3

/

8

Suction Line (in.)

7

/

8

Estimated Charge (lbs)***

M5NE

8 ft

2.7

12 ft

3.9

***This is an average for all refrigerant
types actual refrigerant charge may vary 
by approximately half a pound.

Length (in.) Added to Lineup 
by Each End or Insulated 
Partition

1

/

2

Impact 

M5NGE

Narrow

Meat and Delicatessen

Multi-deck, 5 Display Levels and Front Glass

Dimensions shown as inches and (mm).

NSF Certification

These merchandisers are manufactured to meet ANSI /National 
Sanitation Foundation (NSF

®

) Standard #7 requirements. 

Отзывы: