REFRIGERATION DATA

Note: 

This data is based on store temperature and

humidity that does not exceed 75

°

F and 55% R.H. 

C5X-LE

Meat Produce Dairy

Discharge Air (°F)

29

31 31

Evaporator (°F)

21 24 24

Unit Sizing (°F) 

19

22 22

Btu/hr/ft — Unlit Shelves

C5X-LE

‡‡

Parallel

Conventional

M

EAT

1715

1820

P

RODUCE

1650

1750

D

AIRY

1590

1690

‡‡ Add 10 Btu/hr/ft 

per shelf row

for LED fixtures.

Add 20 Btu/hr/ft 

per shelf row

for fluorescent lamps.

DEFROST DATA

C5X-LE

Frequency Hrs

6

Defrost Water (lb/ft/day)

10.5

(± 15% based on case configuration and product

loading).

O

FFTIME

C5X-LE

Temp Term °F

48

Failsafe Minutes

30

E

LECTRIC OR

G

AS

Not Recommended 

Standard Defrost Thermostat 

Close on rise: close 48°F  —  open 33°F 

CONVENTIONAL CONTROLS

Low Pressure Backup Control

CI/CO

*

C5X-LE

Meat Produce  Dairy

14°F / 4°F

17°F / 7°F

17°F / 7°F

Indoor Unit Only, Pressure Defrost

Termination*

48°F

*Use a Temperature Pressure Chart to determine

PSIG conversions.

Estimated Charge (lb)**

C5X-LE

4 ft

1.6

6 ft

2.2

8 ft

3.1

10 ft

3.8

12 ft

4.5

**This is an average for all refrigerant types.
Actual refrigerant charge may vary by
approximately half a pound.

3 of 8

P/N 0473382_E

HUSSMANN CORPORATION • BRIDGETON, MO  63044-2483 U.S.A. • WWW.HUSSMANN.COM

31 

5

/

(804)

3

/

(120)

30 

1

/

4   

(768)

42

 

(1064)

33 

1

/

(851)

30 

1

/

4

 

(768)

61

 

(1549)

42

 

(1064)

54 

7

/

8

 

(1393)

FAN

L

C5X-LE

17 

1

/

4

 

(438)

3 In. 

(77 mm) 

Required 

Air Gap

81 

3

/

4

 

(2077)

1

/

(183)

19 

5

/

8

 

(499)

5

/

8

 

(92)

26 

1

/

(665)

Refrigeration 
Outlet

7

/

8

 

(123)

Electrical 

Case to Case 

Connections

17 

1

/

(436)

Impact  

Excel

C5X-LE

All

Dimensions shown as in. and (mm).

Multi-deck, 5 Display Levels, Low Front

NSF Certification

This merchandiser model is manufactured to meet ANSI/NSF
(National Sanitation Foundation) Standard #7 requirements for
construction, materials & cleanability.

Содержание impact Excel C5X-LE

Страница 1: ...Fan Assembly 1 0058698 Fan Motor Evaporator MO 4410102 0142780 Fan Blade FB 0142780 7W Energy Efficient Fan Assembly 1 0477654 Fan Motor Evaporator MO 4410545 0142780 Fan Blade FB 0142780 10 Ft uses...

Страница 2: ...1054 29 1 2 750 41 1 2 1054 Distance between edges of center legs NA NA NA 43 7 8 1114 43 7 8 1114 Distance between front legs and splashguard 2 3 4 70 2 3 4 70 2 3 4 70 2 3 4 70 2 3 4 70 Electrical...

Страница 3: ...14 F 4 F 17 F 7 F 17 F 7 F Indoor Unit Only Pressure Defrost Termination 48 F Use a Temperature Pressure Chart to determine PSIG conversions Estimated Charge lb C5X LE 4 ft 1 6 6 ft 2 2 8 ft 3 1 10 f...

Страница 4: ...uorescent 1 Row Canopy 0 26 0 51 0 51 0 77 0 77 30 59 59 85 85 Optional Lighting T 8 Fluorescent Additional 1 Row Canopy 0 26 0 51 0 51 0 77 0 77 30 59 59 85 85 Additional 2 Row Canopy 0 51 1 02 1 02...

Страница 5: ...87 m3 m ARI Total Display Area 3 Sq Ft Ft 4 74 ft2 ft 1 44 m2 m Shelf Area 4 Sq Ft Ft 9 88 ft2 ft 3 01 m2 m 1 Computed using ARI 1200 standard methodology Refrigerated Volume ft3 m3 Unit of Length ft...

Страница 6: ...an Band Standard Lighting 1 Row Canopy Optional Lighting 2 Row Canopy 3 Row Canopy 5 4 5 5 Connector W B BL BL R BL R R R Optional Lighting 1 Row Rail B 4 ft 6 ft or 8 ft 12 ft 4 ft 6 ft or 8 ft 12 ft...

Страница 7: ...components must have mechanical ground and the merchandiser must be grounded CIRCLED NUMBERS PARTS LIST ITEM NUMBERS CASE GROUND Optional Shelf Harness and Light Circuits for Five Rows of Shelves 4 ft...

Страница 8: ...R BL R BL R BL 7 7 7 7 7 7 7 R BL 6 B B W W BL R R BL R BL R BL R BL R BL R BL R BL 7 7 7 7 7 7 7 R BL 6 B B W W BL R R Red G Green BL Blue B Black W White 120V POWER 120V NEUTRAL FIELD GROUND WARNIN...

Отзывы: