REFRIGERATION DATA

Note: 

This data is based on store temperature

and humidity that does not exceed 75

°

F and

55% R.H.

CW2-EGE

Discharge Air (°F)

28

Evaporator (°F)

21

Unit Sizing (°F)

19

Btu/hr/case

CW2-EGE

Parallel

4600

Conventional

5100

DEFROST DATA

CW2-EGE

Frequency (hr)

6

Defrost Water (lb/case/day)

8

(± 15% 

based on a case configuration and

product loading).

O

FFTIME

CW2-EGE

Temp Term (°F)

48

°

Failsafe (minutes)

45

E

LECTRIC OR

G

AS

Not Recommended 

Standard Defrost Thermostat

Close on rise: close 48°F — open 33°F

CONVENTIONAL CONTROLS

Low Pressure Backup Control

CW2-EGE

CI/CO (Temp °F)

*

17°/ 7°

Indoor Unit Only, Pressure Defrost
Termination (Temp °F)*

48°

*Use a Temperature Pressure Chart to
determine PSIG conversions.

PHYSICAL DATA

Merchandiser Drip Pipe (in.)

1

/

4

Liquid Line (in.)

3/8

Suction Line (in.)

7/8

Estimated Charge (lb)**

CW2-EGE

1.7

**This is an average for all refrigerant types.
Actual refrigerant charge may vary by 
approximately half a pound.

Length Added to Lineup by:
Each End/Partition (in.)

1

/

2

3 of 6

P/N 0399452_C

48 

(1219)

Front 

of 

Case

16 in. Shelf

12 in. Shelf

10 

3

/

4

 

(273)

(127)

32 

(813)

3

/

8

 

(162)

26 

(660)

(178)

7

/

8

 

(98)

1

/

2

 

(216)

12 

3

/

8

 

(314)

28 

3

/

8

 

(721)

40 

3

/

4

 

(1035)

FAN

COIL

30 

1

/

8

 

(765)

(127)

21 

(533)

(229)

Dimensions shown as inches and (mm).

Convertible Island End, 2 Display Levels

Impact  

CW2-EGE

Convertible Island End

CW2-EGE

HUSSMANN CORPORATION • BRIDGETON, MO  63044-2483 U.S.A. • WWW.HUSSMANN.COM

NSF Certification

This merchandiser model is manufactured to meet ANSI/NSF
(National Sanitation Foundation) Standard #7 requirements for
construction, materials & cleanability.

Содержание IMPACT CW2-EGE

Страница 1: ...STS C 0135966 Ballast Electronic 3 1 lamp BA 4480883 D 0039764 Lamp Starter EP 4481081 4 E Fluorescent Lamp 5 Replace with like fixtures CW2 EGE Technical Data Sheet P N 0399452_C NSF Certified July 2007 2007 HUSSMANN CORPORATION BRIDGETON MO 63044 2483 U S A U S CANADA 1 800 922 1919 MEXICO 1 800 522 1900 WWW HUSSMANN COM We reserve the right to change or revise specifications and product design ...

Страница 2: ...rical service to O S edge of front base rail 7 178 RH edge of case to center of knockout 46 7 8 1191 Length of electrical raceway 21 3 8 543 Waste Outlet Front RH edge of case to the center of waste outlet 11 7 8 301 Center of waste outlet to outside of front base rail 3 7 8 98 Water Seal Center of case to center of pipe connection 32 813 Outside diameter of the drip pipe 1 1 4 32 Water seal outle...

Страница 3: ...ne PSIG conversions PHYSICAL DATA Merchandiser Drip Pipe in 1 1 4 Liquid Line in 3 8 Suction Line in 7 8 Estimated Charge lb CW2 EGE 1 7 This is an average for all refrigerant types Actual refrigerant charge may vary by approximately half a pound Length Added to Lineup by Each End Partition in 1 1 2 3 of 6 P N 0399452_C 48 1219 Front of Case 16 in Shelf 12 in Shelf 10 3 4 273 5 127 32 813 6 3 8 16...

Страница 4: ...s 120V 60Hz 0 96 NA With Energy Efficient Fans 120V 60Hz See Note 1 below Maximum Over Current Protection 120V 20 Electric Defrost Heaters 208V NA NA Standard Lighting 1 Row Canopy 0 80 40 Optional Lighting 2 Rows Canopy See Note 2 below Optional Shelf Lighting 1 Row of Shelves 0 80 40 2 Rows of Shelves 1 60 80 Note 1 All CW2 end compartments are equipped with energy efficient fan motors as standa...

Страница 5: ... White 120V POWER 120V NEUTRAL Field GROUND WARNING All components must have mechanical ground and the merchandiser must be grounded CIRCLED NUMBERS PARTS LIST ITEM NUMBERS Fan Wiring Offtime Defrost Case GROUND 2 Defrost Termination Thermostat Refrigeration Thermostat Dark Blue To Condensing Unit Light Blue 3 2 Fans 120V NEUTRAL BROWN BAND 120V POWER Fans 1 BROWN BAND ...

Страница 6: ...RTMENT LIGHTING SCHEMATIC Standard canopy lighting and optional shelf lighting are shown 4 4 4 4 4 4 120V POWER 120V NEUTRAL WARNING All components must have mechanical ground and the merchandiser must be grounded Grayed components in 12 ft models only R Red Y Yellow G Green BL Blue B Black W White CIRCLED NUMBERS PARTS LIST ITEM NUMBERS ...

Отзывы: