TEMPERATURE AND DEFROST 

CONTROLLER

SAFE-NET III™

 

USER INSTRUCTIONS

Your refrigerated case uses a Hussmann  
Safe-NET™ III temperature and defrost  
controller to precisely maintain the tempera-
ture and prevent frost buildup on the cooling 
coil. LEDs indicate when the compressor or 
refrigeration is on, when the case is in a defrost 
cycle, if the temperature is outside the desired 
range, or if there is a sensor failure. 

An adjustment knob allows the temperature 
to be set within the configured range and can 
power off the controller and compressor. Your 
controller has been custom-configured to pro-
vide the best temperature and defrost control 
for your chilled or frozen food.

The front of the controller has an adjustment 
knob and status LEDs. The back of the  
controller has connections for sensors and 
switched equipment.

The Safe-NET III controller includes the 
following features and connections.
• Adjustment knob: 

Adjusts the temperature setpoint. 
Turn adjustment knob to OFF to turn off 
refrigeration system. Unplug merchandiser 
from power before servicing the unit.

• Controller LEDs: 

Compressor Powered On LED (green): 
Lights while the compressor is running or 
the refrigeration valve is open. 
Defrost Cycle LED (yellow): 
Lights while the refrigeration coil is 
defrosting. 
Temperature or Sensor Alarm (red): 
Lights if the temperature is too warm or 
too cold. Flashes if a sensor fails.

P/N 0545719_B

 

2-3

HUSSMANN CORPORATION • BRIDGETON, MO  63044-2483  U.S.A.

GSVM Vertical Merchandiser with Doors

Содержание GSVM 4060D

Страница 1: ...VM 4060D Medium Temperature Self Contained Vertical Merchandiser with Doors P N 0545719_B February 2015 Installation Operation Manual IMPORTANT Keep in store for future reference MANUAL IO SC GSVM 406...

Страница 2: ......

Страница 3: ...ORTANT KEEP IN STORE FOR FUTURE REFERENCE Quality that sets industry standards 12999 St Charles Rock Road Bridgeton MO 63044 2483 U S Canada 1 800 922 1919 Mexico 1 800 890 2900 www hussmann com 2015...

Страница 4: ......

Страница 5: ...perature Adjustment 2 7 Typical Sensor to Control Config 2 8 START UP OPERATION Start Up 3 1 Controls and Adjustments 3 1 Load Limits 3 1 Stocking 3 1 Shelf Weight Limits 3 2 MAINTENANCE Care and Clea...

Страница 6: ...ptacle Page 2 1 Replaced Wiring Diagram GSVM 4060D 0528357 ORIGINAL ISSUE NOVEMBER 2012 vi ANSI Z535 5 DEFINITIONS DANGER Indicate s a hazardous situation which if not avoided will result in death or...

Страница 7: ...r shipping damage before and during unloading This equipment has been carefully inspected at our factory Any claim for loss or damage must be made to the carrier The carrier will provide any necessary...

Страница 8: ...NG Unloading from Trailer Lever Bar also known as a Mule Johnson Bar J bar Lever Dolly or Pry Lever Move the merchandiser as close as possible to its permanent location and remove all packaging Check...

Страница 9: ...iser by all four corners Merchandiser s must be installed level to ensure proper operation of the refrigeration system and to ensure proper drainage of defrost water OPTIONAL LEGS NSF approved legs re...

Страница 10: ...the other Sealing of the lower front and rear panels on self contained mod els may hamper their removal for servicing or maintenance of the condensing unit NOTE Do not allow trim to cover any intake...

Страница 11: ...an extension cord 6 Ensure that the proper electrical requirements for the equipment are supplied 7 Verify field electrical connections are tight 8 Verify all electrical wiring is secured and clear o...

Страница 12: ...1 6 Installation NOTES P N 0545719_B U S Canada 1 800 922 1919 Mexico 1 800 890 2900 www hussmann com...

Страница 13: ...be dedicated for the merchandiser Failure to do so voids the warranty Do not use an extension cord Never plug in more than one merchandiser per electrical circuit Always use a dedicated circuit with...

Страница 14: ...ms use a capillary tube for refrigerant control The capillary tube is soldered to the suction line pull out coil for proper heat exchange If the capillary should become plugged or damaged it is best t...

Страница 15: ...ntrol for your chilled or frozen food The front of the controller has an adjustment knob and status LEDs The back of the controller has connections for sensors and switched equipment The Safe NET III...

Страница 16: ...red up or is turned off and then back on a 2 digit Parameter Code Number will display for 3 seconds Then the Self Check will Start 2 Wait for the self check to complete During the self check each LED...

Страница 17: ...even though the refrigeration mode has been initiated The green LED will be lit 2 The compressor will start after a 1 minute delay once power is applied 3 The compressor will continue to run until it...

Страница 18: ...itch to a duty cycle operation During duty cycle operation the refrigeration system will cycle on and off until the sensor is serviced The graph below shows an example of duty cyle operation during a...

Страница 19: ...shows the setpoint cut out value A few seconds after the temperature is set the controller reverts to the sensed temperature in the merchandiser 3 To verify merchandiser settings turn the dial to war...

Страница 20: ...2 8 Installation P N 0545719_B U S Canada 1 800 922 1919 Mexico 1 800 890 2900 www hussmann com...

Страница 21: ...ir temperature shown Measure discharge air temperatures at the center of the discharge honeycomb Defrosts are time initiated and time terminated for self contained The defrost setting is factory set a...

Страница 22: ...LF MAXIMUM WEIGHT LIMITS Hussmann merchandiser shelves are designed to support the maximum weight load limits as indicated in the table below Exceeding these maximum weight load limits may cause damag...

Страница 23: ...on any interior surfaces Do not use high pressure water hoses Do Disconnect electrical power before cleaning Remove the product and all loose debris to avoid clogging the waste outlet Store product i...

Страница 24: ...of the stainless steel finish Do not use bleach CLEANING SOLAR THERMOMETER GSVM models have solar thermometers The thermometer is located at the top front center of the merchandiser s cabinet interio...

Страница 25: ...er failure The evaporation pan waste water will overflow and spill onto the floor if the heater is not properly operating Remove accumulated debris from the evapora tion pan Wipe down heater coil with...

Страница 26: ...ow blockage increases energy consump tion and reduces the merchandiser s ability to maintain operating temperature To clean the coils use a vacuum cleaner with a wand attachment and a soft non metalli...

Страница 27: ...the unit Heat and air registers fans and doors etc x Check for water leaks x Clean evaporator coil s and fan blade s Do not use an acid base cleaner Rinse off any cleaner residue x Clean discharge ai...

Страница 28: ...4 6 Maintenance NOTES P N 0545719_B U S Canada 1 800 922 1919 Mexico 1 800 890 2900 www hussmann com...

Страница 29: ...the correct direction 10 Reinstall display pans Bring merchandiser to operating temperature before restocking CLEANING COILS NEVER USE SHARP OBJECTS AROUND COILS Use a soft brush or vacuum brush to c...

Страница 30: ...rformed by two technicians 5 Rotate the LED fixture to release it from the lamp holder 6 Change LED light and replace with like fixture REPLACING SOLAR THERMOMETER GSVM models have solar thermometers...

Страница 31: ...too warm 4 Refrigerant over charge 5 Low voltage compressor cycling on overload 1 Short of refrigerant 2 Inefficient compressor 3 Coil iced up 1 Defective control 2 Control sensing element not in pos...

Страница 32: ...ble for the GSVM Caster Kit Consists of 5 in braking casters which screw in to the standard threaded holes in the four corners under the cage occupied by the standard leg levelers The kit will add 5 5...

Страница 33: ...dered to be used with the wire partition kit above Wire Basket Kits One kit is available to replace the top 13 in shelf or shelves another is available to replace the bottom 15 in shelf Each kit consi...

Страница 34: ...NOTES P N 0545719_B U S Canada 1 800 922 1919 Mexico 1 800 890 2900 www hussmann com 5 6 Service...

Страница 35: ...afe Net III Display F 65C H159052 Safe Net III Display Interface Cable 0509783 Safe Net III Control Harness 0513058 Compressor Relay T92P7A22 120 0459304 Condensate Pan Heater Relay SPDT NC 120V 03425...

Страница 36: ...ket 0527860 Side Plexiglass End LH RH 0526342 Side Bracket Door LH Sliver 0537797 Side Bracket Door RH Sliver 0537798 Door Closer Kit 2 0527355 Condensing Unit Assy 0528494 Compressor NEK6187Z 1 3hp 2...

Страница 37: ...andiser with Doors Appendix A Technical Data A 3 GSVM 4060D General GSVM 4060D Case Length Note Includes One Pair Ends 40 in 1016 mm Optional End Bumpers One Pair 2 in 51 mm Waste Outlet LH end of cas...

Страница 38: ...at std rating conditions DEFROST DATA Frequency hour GSVM 4060D 6 Offtime Failsafe minutes GSVM 4060D 45 Defrost Termination Temperature Terminated PHYSICAL DATA Refrigerant Charge GSVM 4060D R134a 1...

Страница 39: ...total merchandiser electrical load GSVM 4060D Number of Fans 4W open shell 2 Amperes Watts Evaporator Fans 115V 60Hz 0 12 4 Condensate Pan Heaters 115V 3 350 GSVM 4060D Condensing Unit 115V 1Ph 60Hz S...

Страница 40: ...co 1 800 890 2900 www hussmann com A 6 Appendix A Wiring Diagrams ESTIMATED SHIPPING WEIGHT 2 Self Contained Case with Shipping Crate End GSVM 4060D 520 lb 236kg Included 2 Actual weights will vary ac...

Страница 41: ...BK W RELAY W LEVEL SWITCH NEMA 5 15P BK W LINE 1 LINE 2 COMP NA PHASE FAN PHASE THERMOSTAT SENSOR AIR TEMP THERMOSTAT SENSOR TEMP DEFROST HEATER SAFENET III CONTROL BK BK W BL BK W Y B 1 2 3 4 5 6 7 8...

Страница 42: ...information or other support contact your Hussmann representative Please include the model and serial number of the product Hussmann Corporation Corporate Headquarters Bridgeton Missouri U S A 63044 2...

Отзывы: