 PLEASE NOTE!!!

 

  SAFETY INSTRUCTIONS 

 

(SC 58.17 pro / SC 98.47 pro / SC 53.17 pro / SC 93.47 pro) 

Please note the following for masterclock with time switch functionality:  

 

This manual describes only masterclock features. Time switch relevant description can be 

found in the standard time switch manual! 

 

Only the connection diagram, initial operations and the safety instructions of this manual is 

valid. 

 

!!ATTENTION!!

 

DANGER OF LIFE / RISK OF FIRE AND ELECTRIC SHOCK!!!

 

=> Installation and assembly of electrical equipment must be carried out only by a skilled person!!! 

=> Disconnect device from power supply for wiring and installation purposes!!! 

=> Defective devices have to be put out of service immediately!!!

 

 

Connect the supply voltage/frequency as stated on the product! 

 

Warranty void if housing opened by unauthorised person! 

 

The electronic circuit is protected against a wide range of external influences. Incorrect operating may occur if 

external influences exceed certain limits! 

 

Installation and assembly of electrical equipment must be in accordance with local building and electrical 

codes! 

 

The disposal of the device (and batteries) must be in accordance with the valid environmental and national law! 

SC 58.07 pro (DIN rail mounting – master clock) 

Technical data slave-clock-line (SL) 

Initial operation 

SC 58.07 pro 

 

 

Connection diagram

 

 

Number of lines:  

1  

Output voltage:   

24VDC   

 

 

Output current:   

35mA

 

Conn. terminals:  

17 / 18 

Max. number clocks:  approx. 5 slave clocks 

Output signal:   

Pole changing pulse 

Pulse sequence:  

Normal operation = 1/min 

   

 

 

 

During adjustment = 10/min 

Pulse length: 

 

2 sec. 

(Pulse sequence/length adjustable)

 

 

The time switch is delivered in power back up mode (battery mode).

  

The display shows the power plug symbol [flashing 

].

 

 

Press 

-button for 1 second. The display switches to automatic-mode. 

(Displaying the time and the current status of the slave-clock-line (SL)). 

 

The master clock is already programmed with the current date and time and European 

daylight savings time is activated. The slave-clock-line is preset as follows: Minute-line 

activated / start time 12:00 / Slave-clock-line (SL) is stopped

Power supply master clock (See connection diagram on the left) 

 

Connect the supply voltage/frequency as stated on the product! 

Connection slave-clock-line (SL) => master clock (See connection diagram on the left)

 

 

Connect slave-clock-line to terminal no. 17 and 18 of the master clock. 

SC 58.08 pro (DIN rail mounting – master clock) 

Technical data slave-clock-line (SL) 

Initial operation 

SC 58.08 pro 

 

Connection diagram

 

 

Connection sample 

 

 

 

Number of lines:  

1  

Output voltage:   

Max. 250V~ (potential-free) 

Output current:   

1A 

Conn. terminals:  

2 / 8  

Max. number clocks:  Depends on the slave clocks 

Pulse sequence:  

Normal operation = 1/min 

   

 

 

 

During adjustment = ca. 6/min 

Pulse length: 

 

8 sec. 

(Pulse sequence/length adjustable) 

 

 

PLEASE NOTE: The two relays are 

energized alternately every minute. 

 

The time switch is delivered in power back up mode (battery mode).

  

The display shows the power plug symbol [flashing 

].

 

 

Press 

-button for 1 second. The display switches to automatic-mode 

(Displaying the time and the current status of the slave-clock-line (SL)). 

 

The master clock is already programmed with the current date and time and European 

daylight savings time is activated. The slave-clock-line is preset as follows: Minute-line 

activated / start time 12:00 / Slave-clock-line (SL) is stopped

Power supply master clock (See connection diagram on the left) 

 

Connect the supply voltage/frequency as stated on the product! 

Connection slave-clock-line (SL) => master clock (See connection diagram on the left)

 

 

Connect slave-clock-line to terminal no. 2 and 8 of the master clock.

 

Power supply slave-clock-line (SL) (See connection diagram on the left) 

 

Connect power supply for clock motor(s) to terminals 1 / 9 and 3 / 7 

SC 58.17 pro (DIN rail mounting – master clock with time switch functianality / weekly time switch)  Technical data slave-clock-line (SL) 

Initial operation 

SC 58.17 pro 

 

Connection diagram

 

 

 

Number of lines:  

1  

Output voltage:   

24VDC

 

 

Output current:   

150mA 

Conn. terminals:  

17 / 18 

Max. number clocks:  approx. 20 slave clocks 

Output signal:   

Pole changing pulse 

Pulse sequence:  

Normal operation = 1/min 

   

 

 

 

During adjustment = 10/min 

Pulse length: 

 

2 sec. 

(Pulse sequence/length adjustable) 

 

The time switch is delivered in power back up mode (battery mode).

  

The display shows the power plug symbol [flashing 

].

 

 

Press 

-button for 1 second. The display switches to automatic-mode 

(Displaying the time and the current status of the slave-clock-line (SL)). 

 

The master clock is already programmed with the current date and time and European 

daylight savings time is activated. The slave-clock-line is preset as follows: Minute-line 

activated / start time 12:00 / Slave-clock-line (SL) is stopped

Power supply master clock (See connection diagram on the left) 

 

Connect the supply voltage/frequency as stated on the product! 

Connection slave-clock-line (SL) => master clock (See connection diagram on the left)

 

 

Connect slave-clock-line to terminal no. 17 and 18 of the master clock.

 

SC 98.47 pro (DIN rail mounting – master clock with time switch functianality / yearly time switch) 

Technical data slave-clock-line (SL) 

Initial operation 

SC 98.47 pro 

 

Connection diagram

 

 

 

 

Number of lines:  

1  

Output voltage:   

24VDC

 

Output current:   

300mA

  

Conn. terminals:  

35 / 36

 

Max. number clocks: 

 

approx. 40 slave clocks

 

Output signal:   

Pole changing pulse 

Pulse sequence:  

Normal operation = 1/min 

   

 

 

 

During adjustment = 10/min 

Pulse length: 

 

2 sec. 

(Pulse sequence/length adjustable) 

 

The time switch is delivered in power back up mode (battery mode).

  

The display shows the power plug symbol [flashing 

].

 

 

Press 

-button for 1 second. The display switches to automatic-mode 

(Displaying the time and the current status of the slave-clock-line (SL)). 

 

The master clock is already programmed with the current date and time and European 

daylight savings time is activated. The slave-clock-line is preset as follows: Minute-line 

activated / start time 12:00 / Slave-clock-line (SL) is stopped

Power supply master clock (See connection diagram on the left) 

 

Connect the supply voltage/frequency as stated on the product! 

(Master clock = terminals 22/23 / Time switch = terminals 4/5). 

Connection slave-clock-line (SL) => master clock (See connection diagram on the left)

 

 

Connect the slave-clock-line (SL) to the master clock on terminals 35 and 36

  

SC 53.17 pro (19”-housing –   master clock with time switch functianality / weekly time switch) 

Technical data slave-clock-line (SL) 

Initial operation 

SC 53.17 pro 

 

Connection diagram

  

 

SC 53.17: 2 NU-Linie 

The signal output for line 1 and line 2 can be configured 

independently to emit pulses either every second or every minute! 

 

 

 

NOTE! Power supply from a third party supplier: 

The usage of a switched-mode power supply to drive the slave clock line 

might disturb the reception of the FU 20.00 pro radio receiver. If the radio 

receiver has no reception (the green LED on the bottom of the radio 

receiver flashes rapidly or not at all)  please connect GND of your 

switched-mode power supply via an Y-capacitor with protective earth. 

Number of lines:  

 

Input U

SL

:   

 

24VDC (12VDC/48VDC/60VDC)

 

   

 

 

 

(Monitoring U

SL

 - switchable)

 

Output current:

   

up to 1500mA for each line

 

   

 

 

 

(Depends on the power supply)

 

Conn. terminals:  

See conn. diagram on the left

 

Max. number clocks: 

 

approx. 200 slave clocks 

   

 

 

 

(each line)

 

Output signal:   

Pole changing pulse 

Pulse sequence:  

Normal operation = 1/min 

   

 

 

 

During adjustment = 10/min 

Pulse length: 

 

2 sec. 

(Pulse sequence/length adjustable) 

Module:  

 

 

NT 73 (Power adapter slave line) 

   

 

 

 

           

Not included in delivery!

 

 

The time switch is delivered in power back up mode (battery mode).

  

The display shows the power plug symbol [flashing 

].

 

 

Press 

-button for 1 second. The display switches to automatic-mode 

(Displaying the time and the current status of the slave-clock-line (SL)). 

 

The master clock is already programmed with the current date and time and European 

daylight savings time is activated. The slave-clock-line is preset as follows: Minute-line 

activated / start time 12:00 / Slave-clock-line (SL) is stopped

Power supply master clock (See connection diagram on the left) 

 

Connect the supply voltage/frequency as stated on the product! (Terminals 32a und 32c). 

Connection power supply the slave-clock-line (SL) => master clock

  

(See connection diagram on the left)

 

 

Depending on the specifications of the slave clocks, connect 12VDC; 24VDC; 48VDC; or 

60VDC to terminals 26a and 26c. 

 

Check polarity. 

 

For voltages of slave clocks which differ from 24VDC, the dip switches on the PCB have to 

be configured as stated within the table on the left

Connection slave-clock-line (SL) => master clock (See connection diagram on the left)

 

 

Connect slave-clock-line to:

 

Line 1 [L1] => terminals 24a und 24c  

Line 2 [L2] => terminals 22a und 22c

 

Table dip switches 

 

(Power supply monitoring of the slave-clock-

line) 

SL   

S1   

S2 

SL   

S1   

S2 

 

12VDC  ON   

ON 

 

48VDC  OFF 

ON 

 

24VDC  ON   

OFF 

 

60VDC  OFF 

OFF 

SC 93.47 pro (19”-housing –  master clock with time switch functianality / yearly time switch) 

Technical data slave-clock-line (SL) 

Initial operation 

SC 93.47 pro 

 

Connection diagram

  

 

 

 

NOTE! Power supply from a third party supplier: 

The usage of a switched-mode power supply to drive the slave clock line 

might disturb the reception of the FU 20.00 pro radio receiver. If the radio 

receiver has no reception (the green LED on the bottom of the radio 

receiver flashes rapidly or not at all)  please connect GND of your 

switched-mode power supply via an Y-capacitor with protective earth.

 

Number of lines:  

1  

Input U

SL

 

 

24VDC (12VDC/48VDC/60VDC) 

   

 

 

 

(Monitoring U

SL -

 switchable) 

Output current: 

 

up to 1500mA

 

   

 

 

 

(Depends on the power supply)

 

Conn. terminals:  

See conn. diagram on the left

 

Max. number clocks: 

 

approx. 200 slave clocks

 

Output signal:   

Pole changing pulse 

Pulse sequence: 

 

Normal operation = 1/min

 

   

 

 

 

During adjustment = 10/min

 

Pulse length:

 

 

2 sec.

 

(Pulse sequence/length adjustable) 

Module: 

 

 

 

 NT 73 (Power adapter slave line) 

   

 

 

 

            

Not included in delivery!

 

 

The time switch is delivered in power back up mode (battery mode).

  

The display shows the power plug symbol [flashing 

].

 

 

Press 

-button for 1 second. The display switches to automatic-mode 

(Displaying the time and the current status of the slave-clock-line (SL)). 

 

The master clock is already programmed with the current date and time and European 

daylight savings time is activated. The slave-clock-line is preset as follows: Minute-line 

activated / start time 12:00 / Slave-clock-line (SL) is stopped

Power supply the master clock (See connection diagram on the left) 

 

Connect the supply voltage/frequency as stated on the product! (Terminals 32a und 32c) 

Connection power supply slave clockline => master clock

  

(See connection diagram on the left)

 

 

Depending on the specifications of the slave clocks, connect 12VDC; 24VDC; 48VDC; or 

60VDC to terminals 26a and 26c. 

 

Check polarity. 

 

For voltages of slave clocks which differ from 24VDC, the dip switches on the PCB have to 

be configured as stated within the table on the left

Connection slave-clock-line (SL) => master clock (See connection diagram on the left)

 

 

Connect slave-clock-line to terminal no. 24a and 24c of the master clock.

 

Table dip switches 

 

(Power supply monitoring of the slave-clock-

line) 

SL   

S1   

S2 

SC   

S1   

S2 

 

12VDC  ON   

ON 

 

48VDC  OFF 

ON 

 

24VDC  ON   

OFF 

 

60VDC  OFF 

OFF 