background image

 

 

Luxstat Low Voltage Wall Switches 
 
Installation and Operating Instructions 

 

Hubbell Building Automation 

9601 Dessau Road 

 Building One 

 Suite 100 

Austin, TX 78754 
Toll Free: 888-698-3242 

 Fax: 512-450-1215 

www.hubbell-automation.com 
 

DESCRIPTION 

The Luxstat Low Voltage Wall Switches are 
designed to provide a user interface and control of 
Luxstat Daylighting Control Modules. With a 
configuration that fits standard, single gang wall 
boxes and an architecturally pleasing appearance, 
these devices provide a solution for applications 
where low voltage switch input is required.   
 

SPECIFICATIONS

 

• 

Supply voltage: 24VDC 

• 

Pilot LED Current: 10mA Nom. @ 24VDC 
(LUXSTATSW2AUTO and LUXSTATSW4 
versions only) 

• 

1, 2 and 4 button versions available 

• 

Accepts standard decorator style wall plate (Not 
Included) 

• 

Available in White or Ivory 

• 

Fits standard single gang wall box 

• 

Two-year warranty 

 

PRECAUTIONS 

• 

CAUTION:  FOR USE WITH CLASS 2, 
LOW VOLTAGE SYSTEMS ONLY.  DO 
NOT USE IN HIGH VOLTAGE 
APPLICATIONS. 

 

• 

Read and understand all instructions before 
beginning installation. 

 

• 

NOTICE:  For installation by a licensed 
electrician in accordance with National and/or 
local Electrical Codes, the instructions of the 
system to be interfaced with, and the following 
instructions. 

 

• 

NOTICE:  For Indoor use only. 

 

• 

CAUTION:  USE COPPER CONDUCTOR 
ONLY. 

 

• 

Confirm device ratings are suitable for 
application prior to installation.  Use of device in 
applications beyond its specified ratings or in 
applications other than its intended use may 
cause an unsafe condition and will void 
manufacturer’s warranty. 

 

• 

NOTICE:  Do not install if any damage to 
product is noticed. 

 

INSTALLATION 

1.  Prepare the installation site, as necessary, to 

install the Luxstat Wall Switch. 

 
2.  Route 18 AWG, Class 2 cable with a quantity of 

conductors sufficient (Table 1) for the Luxstat 
control module to the wall switch location. 
Maximum lead length must not exceed 150 feet. 

 

Luxstat Switch 

# Cable Conductors 

LUXSTATSW1 2 

LUXSTATSW4 

7 – LUXSTATDCM 
5 – LUXSTATOCM 

LUXSTATSW2AUTO 5 
LUXSTATSW2DIM 3 

 

Table 1

 – Number of cable conductors needed 

per switch. 
 

Note:

  Low voltage wiring 

must be

 isolated from 

line voltage wiring.  Consult National and Local 
Electrical Codes for conduit requirements. 
 

3.  Wire the Luxstat Wall Switch to the Luxstat 

controller according the controller’s instructions 
and the appropriate Wiring Diagram below. 

 

Note:

  Wiring Diagrams can also be found at 

www.hubbell-automation.com

 
4.  Install the Luxstat Wall Switch into the wall box 

using the mounting screws provided.  For Luxstat 
Wall Switches with multiple buttons, note proper 
“up” orientation as shown on the product label.  
Install decorator style wall plate (not included). 

 
5.  Perform system setup and/or programming 

activities as applicable in accordance with the 
instructions of the Luxstat control module. 

 