                                                                 Data Monitoring 

 

 

 

Ethernet Gateway 

User’s Manual 

Version 1.0

 

 
 
 
 

                        

           

 

 
 

 

 
 
 
 
 
 
 
 
 
Wiring Device 

– Kellems 

Hubbell Incorporated (Delaware) 
Shelton, CT 06484 
1-800-288-6000 

www.hubbell-wiring.com

 

Содержание HBLGW04000EUS1

Страница 1: ...PD2864 9 18 Data Monitoring Ethernet Gateway User s Manual Version 1 0 Wiring Device Kellems Hubbell Incorporated Delaware Shelton CT 06484 1 800 288 6000 www hubbell wiring com ...

Страница 2: ...ta Output from SNMP Gateways 28 Accessing the Gateway Console 29 Accessing the MIB files from Gateway Console 29 Accessing active OIDs 31 Viewing monitoring node readings on the Gateway Console 32 Uploading an SNMP license to the Gateway 33 Enabling and configuring the SNMP Agent 34 Using the iReasoning MIB browser 35 Virtual IP addressing Assigning Virtual IPs to monitoring nodes 40 Modbus TCP IP...

Страница 3: ...e IDs 52 Accessing and Verifying Modbus Readings Using the Gateway Console 54 Exporting Modbus Readings 55 MTConnect Implementation 56 EthernetIP Implementation 57 Technical Specifications 59 Regulatory Information and Labels 60 Regulatory Information 60 Regulatory Label 61 ...

Страница 4: ...n the local Ethernet network If the monitoring application is gathering data using SNMP or Modbus protocols some additional steps are needed that are specific to each of those protocols Gateway Models Model Number Description Protocol Monitoring units HBLGW04000EUS1 HBLGW04000LUS1 Ethernet Gateway V4 EMX 100 30 HBLGW0400MEUS1 HBLGW0400MLUS1 Ethernet Gateway V4 Modbus Modbus TCPIP 100 30 HBLGW0400S...

Страница 5: ... the IP address make sure that you have the following data provided to you by your IT administrator 1 IP Address 2 Gateway 3 Netmask 4 DNS Using the Joystick to navigate If the Gateway is new and does not have an IP address you can enter the IP address directly onto the Gateway using the on board joystick selector button and display After the Gateway is energized and completes its boot sequence ap...

Страница 6: ...as a default DHCP addressing relies on the server to automatically assign the IP information eliminating the need to manually input the IP addressing To enable manual IP addressing as required in most cases it is necessary to turn DHCP off by following the menu instructions below When DHCP is turned off the configuration menu will reveal options for inputting IP address information Entering IP add...

Страница 7: ...ing a standard web browser and entering the IP address of the Gateway This requires that the Gateway be connected via Ethernet network router or switch Under some circumstances the Gateway can be accessed and configured directly from a PC but many enterprise systems prevent external IP addressing functions on a PC The Gateway console is described in greater detail online at https dox packetpower c...

Страница 8: ...ystem tab sub menu click the Networking tab If DHCP is on you will not be able to access any network setting until it is switched off under the Network Interface section When DHCP is turned off the network settings will be revealed in the Network Interface section It is now possible to modify the IP address Netmask Gateway addresses ...

Страница 9: ...e top right of console For more information on available NTP servers see the NTP server section The time will be expressed in the top right corner of the Console screen Configuring Data Destinations Data Destinations configures how the Gateway delivers data The Gateway can make monitoring data accessible via three formats 1 EMX Monitoring Portal Note data can be provided simultaneously to the EMX ...

Страница 10: ...ault for both Monitoring Data Feed and Upgrade and Support Data Feed sections 5 Ensure that the Gateway s IP address has outbound access to port 80 HTTP or 443 HTPPS for amazonaws com when using cloud EMX 6 Confirm that cloud and support data feeds are enabled with the network manager cloud EMX implementations only 7 For local EMX implementation enter the IP address of the server 8 Before you can ...

Страница 11: ...ays try and locate the Gateway at the highest point that allows an unobstructed line of sight path to monitoring nodes Redundant Gateways are advised for any critical environment One Gateway can support up to 150 Hubbell monitoring devices additional Gateways will improve polling speeds If you are placing multiple Gateways for better coverage or redundancy try to space them approximately evenly th...

Страница 12: ...ail clip which snaps onto the receiver clip on the back of the Gateway The rubber bumpers on the back of the Gateway mount can be removed to expose 0 20 holes which can be used for permanent mounting with mechanical fasteners Adhesive tabs allow the Gateway to be wall mounted or surface mounted away from metallic surfaces like server cabinets Orientation of the Gateway is not critical ...

Страница 13: ...installations Power over Ethernet PoE adapters using a PoE splitter that plugs into the DC jack cannot be powered by PoE in the Ethernet jack USB power adapter cable for powering from any USB port power only no data connection is made If powering using PoE Power over Ethernet A PoE splitter is required as the Gateway will not accept a PoE source directly into its Ethernet port Be sure that the PoE...

Страница 14: ...including the Panel Editor for defining branch circuit panel maps Data Destinations configures the Gateway for data access via Modbus TCP IP SNMP and the EMX Portal System manage system settings such as IP addresses and firmware versions Status The Status page provides a general overview of all critical Gateway functions as well as links to key sections required for configuration 1 System Status I...

Страница 15: ...ccess to various Gateway settings and tools Monitoring Data The Monitoring Data tab exposes all the nodes monitors associated with the Gateway The sub menu will show associated nodes by type power or environmental along with their GUID 1 Clicking on a specific node ID will expose the readings for that node Likewise the readings for a specific node can also be exposed by clicking on the readings ic...

Страница 16: ... Readings per minute or the frequency of data reports received from the node each minute This will vary depending on the strength of the radio signal and ratio of node to Gateways Age Duration online Readings Exposes readings from the device RPM Readings per Minute and Reporting Frequency The reporting frequency of wireless nodes to the Gateway is a function of how many nodes share the Gateway and...

Страница 17: ...s checked Name Friendly name description Type Gateway model EG3 or EG4 of peer Gateway IP Address IP address of peered Gateway Port Network port typically port 80 4 Click the green Add button to complete the process It will now be possible to extract data for the peered Gateway from this Gateway Note that each Gateway must have peering data completed in order to receive data from other Gateways an...

Страница 18: ...ased version and in some instances EMX may be installed as a local application Select the version of EMX to be implemented in the Monitoring Data Feed and Upgrade and Support Data Feed sections Note that Cloud EMX is the default selection Cloud EMX Ensure that the Gateway s IP address has outbound access to port 80 HTTP or 443 HTTPS for amazonaws com when using cloud EMX Confirm that cloud and sup...

Страница 19: ...ction System The following resources are accessible under the System menu Dashboard The Dashboard feature is a diagnostic tool for use by Hubbell and authorized partners It may not be exposed on all Gateways Networking The Networking tab allows for the input of network settings See the Network Configuration section for a detailed explanation ...

Страница 20: ...Hubbell Ethernet Gateway V4 User s Manual PD2864 9 18 Page 19 Authentication Configure your desired method of authenticating user access to the Gateway Several options exist including None ...

Страница 21: ... is necessary to enter the Certificate and Key files 2 for the related protocols Once the data has been entered click the Save button to implement Additional security options are available Consult Hubbell for details Radio Zone WARNING DO NOT update any Radio Zone settings without consulting Hubbell You may permanently disable your system and or violate local radio communication licenses Hubbell G...

Страница 22: ...ge has been received and verified to be correct Due to the variability of the radio connections and network load firmware updates may take from a few hours to a day depending on the size of the network During the update process the monitors will continue to function normally When completed the monitors will automatically reboot and switch to new firmware Note that different monitoring node types u...

Страница 23: ...ve with the newer firmware version The node may be offline for a very short time during the reboot process In the event that a firmware upload is interrupted it will resume at its last position without losing the initial data uploads The upload status can also be viewed on the main Gateway Console screen next to the System Status indicator System Update Update Firmware on Gateway The System Update...

Страница 24: ...re provided from Hubbell 2 Click the Upload button 2 The system upgrade may take upwards of 30 minutes System Firmware Selection The System Firmware Selection tab allows users to implement alternate versions of firmware residing on the Gateway The firmware must be loaded onto the Gateway using the System Update feature To change a Gateway firmware operation version ...

Страница 25: ...eatures include SNMP Modbus Virtual Panel Mapping Gateway Capacity limited versus standard Monitor Mode To implement a product license 1 Select the license file by clicking on the choose file button under Select License File 1 2 Click on the Upload button 3 A reboot of the device will be required to make the license effective Reboot In some cases the Gateway may require rebooting To reboot the Gat...

Страница 26: ...ional details relating to the Gateway operation They are retrieved for debugging purposes and used strictly by Hubbell engineers To obtain a log file 1 Select the Logs tab from the System menu on the right hand task bar 2 Select the log to be accessed under the View debug log menu The log file will then appear in the dialog box where it can be copied and pasted as required Note that there are six ...

Страница 27: ...Hubbell Ethernet Gateway V4 User s Manual PD2864 9 18 Page 26 ...

Страница 28: ...ades The Ethernet Gateway Version 4 provides a means of performing firmware upgrades to both itself and to most Hubbell wireless monitoring units Upgrades are performed via the System page of the web console Detailed instructions can be found in the Web Console System section ...

Страница 29: ...tact techserv hubbell com Required Files and Tools MIB Files MIB files can be downloaded directly on the Gateway or from the links below General MIB File click to download MIB file for use with VIPs Virtual IP addressing click to download iReasoning Browser iREasoning MIB Browser is a utility that allows you to view MIB files Data Output from SNMP Gateways Requirements Download iREasoning MIB Brow...

Страница 30: ... that the system is communicating properly with the monitoring nodes as indicated by a green status light 4 Click the link under Wireless Mesh to see monitoring nodes that are currently communicating with the Gateway 5 SNMP Data will be able to be viewed through the SNMP data link this light will be green once the SNMP agent is enabled Accessing the MIB files from Gateway Console MIB files can be ...

Страница 31: ...B file On the Gateway console go to Data Destinations SNMP on the left menu and then click on the standard MIB file Downloading the MIB file for use with virtual IP addressing On the Gateway console go to Data Destinations SNMP Nodes on the left menu and then click to download the MIB file ...

Страница 32: ...compatible format This will vary as nodes are added and removed from the system OID lists are used with systems utilizing explicit tag lists of monitoring points e g KEPServer or whenever you need SNMP access to a specific set of readings To access the file go to the Data Destinations tab on the left menu and select SNMP On the main screen select the button Export OID List CSV This will download t...

Страница 33: ... node readings on the Gateway Console 1 Confirm that monitoring nodes are active and returning data to the Gateway by selecting the Monitoring Data tab this will display all connected nodes 2 Click on the readings icon to expose the real time readings for a specific monitoring node ...

Страница 34: ...e file button under Select License File in the System menu 2 Click on the Upload button and point to the location of the license provided by Hubbell A reboot of the device will be required to make the license effective The reboot tab can be found under the System menu In the event that SNMP is not a licensed feature you will need to obtain a license from Hubbell techserv hubbell com ...

Страница 35: ... enabled in the check box 3 Select the correct SNMP version This guide is for SNMP V1 and V2 for SNMP V3 implementation see the SNMP 3 guide 4 Set the Agent port to 161 or as needed 5 The Community read string used for authentication should be public 6 Click Save to save settings 7 The SNMP status light in the left menu will be green indicating the onboard SNMP agent is active ...

Страница 36: ...the SNMPv2 MIB file if using SNMP V2 For older SNMP versions use the appropriate MIB file supplied in the MIB directory This file will automatically be supplied with iReasoning in the mibs directory Loading Gateway and node MIB files on to the iReasoning browser 1 Load the MIB for Gateway and monitoring nodes using the Load MIBs function under the FILE menu 2 PACKETPOWER EG4 MIB is for the Gateway...

Страница 37: ...IB files on the iReasoning Browser The SNMP management MIB can be found under the mgmt file of the MIB tree The Gateway MIB file can be found under the eg4 directory under the private directory The monitoring nodes MIB file can be found under the monitoringNode directory under the private directory ...

Страница 38: ...ublic 4 Confirm port is correct 161 5 Confirm that the SNMP version matches the settings used on the Gateway Console SNMP settings i e SNMP version Leave Write Community blank Confirming communication with the Gateway 1 Check the system description by clicking on the the SysDescr file on the MIB tree mgmt mib 2 SysDescr 2 Right click on the sysDescr file and and select Get from the pop up menu 3 T...

Страница 39: ...for proper communications 2 Node GUIDs will be displayed in the table these node IDs will correspond to the Node IDs on the Gateway Console To see the data in a more structured format use Table View Generating readings tables and nodes tables Table View 1 2 To get data in a more structured format select the readingsTable or nodesTable under the EG4 directory private packetPower 3 Right click and s...

Страница 40: ... Nodes Readings Table Readings for all Nodes 1 Performing a TableView on Readings Table by selecting the readingsTable file right click and select Table View from the pop up menu it will reveal a listing of all readings for all nodes associated with the Gateway 2 Node IDs will correspond to the node readings on the Gateway Console accessed by selecting the Monitoring Data menu and highlighting the...

Страница 41: ...g OID will always correspond to a specific channel for specific node ie energy on phase A for a particular node Virtual IP addressing Assigning Virtual IPs to monitoring nodes Monitoring nodes and the Gateway will show up under a single IP address Many monitoring systems using SNMP require that each device node have a unique IP address It is possible to assign a Virtual IP address to each monitori...

Страница 42: ...er the Data Destinations menu then select the Nodes menu This will expose all of the nodes for the Gateway 1 Click on the icon to reveal the Virtual IP addressing pop up 2 Select the Node to be addressed using the drop down Node menu nodes are identified by their 16 digit GUID Enter a virtual IP address this must be valid within the network its being used on Click Add to save Repeat for all nodes ...

Страница 43: ...ations menu IPs will become visible at the same port as the Ethernet Gateway The Gateway will have a unique IP and agent and each node will have a unique IP and agent Viewing nodes by Virtual IP address on iReasoning Browser 1 Enter VIP in the address tab 2 Go to SysDescr file in the MIB tree under the mgmt mib 2 system folders and right click for a Get 3 The monitoring node s ID will be returned ...

Страница 44: ... browser tool to view different IP addresses Viewing node Readings by Virtual IP address on iReasoning Browser 1 Using the same VIP for the particular node in the IP Address bar highlight the mnReadings Table MIB under monitoringNode file Right click and select Table View this will expose the readings table for the specific monitoring node in the table view 2 These readings correspond to those on ...

Страница 45: ...of measurement i e Watt hours mnTime Stamp Time when the value was received Turning Windows Firewall off Windows Firewall will block the iReasoning MIB browser from accessing other IP addresses such as virtual IP addresses To disable the Firewall Windows 10 select control panel all control panel items windows firewall and turn the firewall off for both public and private networks This does not hav...

Страница 46: ...ortals features while also serving data to the third party monitoring system The Ethernet Gateway appears as a standard Modbus device listening on port 502 at the IP address of the Gateway Individual monitoring nodes have distinct Modbus slave IDs If more than 254 nodes are present multiple nodes may report at the same slave ID under different register ranges see Register Mapping section below The...

Страница 47: ...r on an accessible network It may not be accessible directly through a PC Ethernet to Gateway connection in all cases 3 Enter the IP address of the Gateway on any browser to access the Gateway Console Once the Console appears it will present a System status screen Validate 1 The system is communicating properly with the monitoring nodes as indicated by a green status light 2 Modbus is listed as a ...

Страница 48: ...nable the Modbus driver select Modbus tab under the Data Destinations menu in the Gateway Console 2 Make sure that the Enabled check box 2 is checked 3 Enter the port number to be used This is typically port 502 Click Save to enable the selections 4 Once enabled there will be a green light next to the Modbus tab ...

Страница 49: ...ration of specific nodes select the Monitoring Data tab 1 on the Gateway Console This will display all connected nodes which are organized by type power and environmental in the sub menu To search for a specific node enter the GUID 16 digit node ID in the Node tab 2 To access specific readings for each node click on the readings icon to expose the real time readings Register Maps Accessing Registe...

Страница 50: ...itor Three phase power monitor Your register maps can be imported if they are not pre populated Importing and Exporting Register Maps 1 To import a register map select the Register Maps tab under the Data Destinations Modbus menu 2 Click on the utility icon under the Modbus Register Maps table Highlight the import tab and specify the register file to be imported the map will appear in the Modbus R...

Страница 51: ...dity of the register if the register is reading properly it will have a green check mark Manually Assigning Registers and Register Maps Creating Register Maps Individual registers can be added or removed as needed To create a new register map 1 Select the Register Maps tab from the menu under Data Destinations Modbus 2 Select the icon on the Modbus Register Maps table and provide a Map Name and De...

Страница 52: ...18 Page 51 Creating Registers 1 To access and add registers select the Register Maps menu and highlight the specified register map 2 Click on the pencil icon under the Register Maps table this will expose the registers Adding Registers to Register Maps ...

Страница 53: ...odbus interface uses multiple Modbus slave IDs and if necessary register offsets Automatically assigning different host IDs to each nodes allows each node to have an identical register map The number of host IDs is limited to 254 1 254 For installations larger than 254 nodes register offsets are used Each register map is contained within a 200 register window 0 199 The register map however can be ...

Страница 54: ...customized if necessary Note the Map all nodes button will remove all existing Slave ID mappings and re assign them in the order of Node ID If you want to preserve your existing Slave ID assignments e g when you add more monitoring nodes to the system you should edit the node mapping table directly using the edit function at the bottom of the node mapping table ...

Страница 55: ...cessing and Verifying Modbus Readings Using the Gateway Console To access and verify Modbus readings Select the Readings tab under Data Destinations Modbus Register Maps Readings A table containing all Modbus readings will be displayed allowing for easy verification ...

Страница 56: ... Modbus Readings 1 Readings can also be exported by selecting the utility icon and selecting export all readings The files are exported in CSV format and can be viewed in a standard spread sheet Note that readings should match the readings shown in the Monitoring Data tab ...

Страница 57: ...Hubbell Ethernet Gateway V4 User s Manual PD2864 9 18 Page 56 MTConnect Implementation ...

Страница 58: ...Hubbell Ethernet Gateway V4 User s Manual PD2864 9 18 Page 57 EthernetIP Implementation ...

Страница 59: ...Hubbell Ethernet Gateway V4 User s Manual PD2864 9 18 Page 58 ...

Страница 60: ...Hubbell Ethernet Gateway V4 User s Manual PD2864 9 18 Page 59 Technical Specifications ...

Страница 61: ...tion 15 19 of the FCC Rules This device complies with part 15 of the FCC Rules Operation is subject to the following two conditions 1 This device may not cause harmful interference and 2 this device must accept any interference received including interference that may cause undesired operation Pursuant to Part 15 21 of the FCC Rules any changes or modifications to this product not expressly approv...

Страница 62: ...ndustrie Canada le présent émetteur radio peut fonctionner avec une antenne d un type et d un gain maximal ou inférieur approuvé pour l émetteur par Industrie Canada Dans le but de réduire les risques de brouillageradioélectrique à l intention des autres utilisateurs il faut choisir le type d antenne et son gain de sorte que la puissance isotrope rayonnée équivalente p i r e ne dépasse pas l inten...

Отзывы: