background image

LED ON = OK

Figure 3: Diagnostic Operation

Figure 4: Dimensions

3.75

[95]

3.60

[91]

3.00

[76]

0.87

[22]

2.67

[68]

Dimensions:

in.

[mm]

Single-phase 3-wire 

(+GND) 120/240 Vac

 

0.5 in. [13 mm] knockout (trade size)

Actual hole size 0.875 in. [22 mm]

 

an accessible location (not within walls).

1.  Turn off all power supplying this equipment before working on or  

 

inside equipment.

2.   For mounting, see Figure 1.
3.  Confirm SPD is rated for your system by comparing voltage 

 

measurements to the Line Voltage (L-L, L-N) on the product label.

4.   Confirm the black wires are connected to line wires, the white wire

to the neutral wire and green wire to ground (see figure 2). For the

5.   Twist conductors 1/2 turn or more for every 12 inches of length.
6.   Keep conductor length as short as possible with no sharp bends.
7.   Do not loop or coil wires.
8.   Use on solidly grounded systems only.

General Specifications

Short Circuit Current Rating

25 kA

I

Enclosure Rating

Type 4X

Product Weight

1.8 lbs (0.9kg)

Connection Method

Parallel, #12 AWG Solid Wire

Thermal Fusing

Yes

Operating Temperature 

-40° to +160° F (-40° to +70° C)

Operating Frequency 

50/60 Hz

Diagnostics 

Green Status LED per line

Product Standards 

UL 1449-3rd Edition, CSA C22.2 No. 8-M1986,

 

 

Figure 1:  Mounting Unit

 

Single-phase 2-wire 

(+GND) 120 Vac

INSTALLATION

VPR

700V L1-N, 700V L1-G, 700V L2-N, 800V L2-G

System Voltage

120/240VAC

MCOV

150VAC

Product Rating 

Type 1 SPD

(n)

CSA C233.1-87 and CE

Nut

NOTE: The Surge Protective Device must be installed in

Black

Green

Black

White

L1

N

L2

Green

Black

White

L

N

LED ON = Normal Operation

LED OFF = Check breakers and connections.

Verify line voltage at point of SPD connection; 

Iif all correct replace SPD

Panel

0.5 in. [13 mm] knockout (trade size)

Actual hole size 0.875 in. [22 mm]

single-phase, 120/240V 3-wire application, connect one of the SPD

black wires to L1 and the other black wire to L2.  For the single-

phase, 120V 2-wire application, connect both SPD black wires

to the same line.

Figure 2 :  Wiring Diagrams

LED OFF = Fault, 

 

L1 and/or L2

1. Suitable for use on a circuit capable of delivering not more than 25 kA rms symmetrical Amperes.
2. Contains no serviceable parts.

10kA (L1-N, L1-G, L2-N, L2-G)

 

 

Models

Voltage

Mounting

HBL3W120

Side Nipple

120/240 

Side Nipple

HBL3W50

Surge + Overvoltage

Protection

Surge + Overvoltage

Max Surge

Current

120kA

50kA

 

120/240 

2

Hubbell Modular Panel Surge Protective Device (SPD)

Hubbell Hardwired Surge Protective Device (SPD)

INSTAllATION

Electrical equipment should be installed, operated, serviced, and maintained only by qualified personnel. 
No responsibility is assumed by Hubbell for any consequences arising out of the use of this material.

Hubbell Wiring Devices 

1-800-729-3406 | www.Hubbell-Wiring.com