Industrial Lighting
®
1
4
7
1
4
7
1
4
7
1
1
9
10
11
FIGURE 1a
FIGURE 1b
FIGURE 1c
FIGURE 1d
FIGURE 1e
HBL – INDUSTRIAL LED HIGHBAY
INSTALLATION INSTRUCTIONS
SEE WARNING ON CARTON
WARNINGS:
This product contains chemicals known to the state of California to
cause cancer, birth defects and/or other reproductive harm.
Thoroughly wash hands after installing, handling, cleaning, or
otherwise touching this product.
Contact Hubbell Lighting, Inc. for information and direction before re-
lamping or replacing this light fixture.
Disconnect power before installing or servicing.
Install, operate and maintain to meet all applicable codes.
Protect all wiring connections with approved insulators (by others).
Selected fixture voltage must match supply line voltage.
GENERAL INFORMATION, CONDUIT MOUNT:
All 12” (304.8 mm) minimum supply wire outside of conduit.
Fixture housing conduit threads are 3/4-14 NPS or 1-11 ½ NPS.
Use a waterproof pipe joint compound (by others) for all entries into
housing.
Plug all unused entries into housing (if applicable).
PENDANT/CONDUIT & CONE MOUNT: (See Figures 1a,
1b, 2, and 3)
1.
To ease installation, top cover (1) should be removed from the fixture
assembly. Unfasten the latch (2) and the top cover casting can be
removed from the hinge pin assembly (3).
2.
Feed electrical supply wire through the center threaded hole in the top
cover and thread top cover onto conduit until tight.
3.
Tighten set screw located on conduit hub inside the cover to prevent
fixture rotation.
4.
Fixture ground wire connection can be made with supply ground at this
point if desired.
5.
Lift fixture assembly and place the hinge pin (3) in the cradle (4) of the
top cover casting. The fixture can now hang from the hinge pin.
6.
Make remaining wiring connections. See appropriate WIRING
SCHEMATIC for reference. If ground wire was not connected earlier,
connect the fixture ground with the incoming ground wire. There will
be a single white and a single black wire providing power to the entire
array of LED drivers. Incoming power to be connected to the white
wire and the black wire. See warnings above about wire connections.
7.
Dress wires as needed.
8.
Gently pivot the assembly up until the lower portion of the fixture is
against the top cast cover. The lower portion of the fixture should
“nest” inside the fixture cover (1). The orange sealing gasket (5)
should compress evenly as well.
9.
Swing wire bail of the latch (6) over the top cover at the latching point
(7).
10. Press the latch lever (8) to draw the two halves of the fixture together
and seal.
STRAIGHT STANCHION/POLE MOUNT: (See Figures 1c,
2, and 3)
1.
To ease installation, top cover (1) should be removed from the fixture
assembly. Unfasten the latch (2) and the top cover casting can be
removed from the hinge pin assembly (3).
2.
Feed electrical supply wire from the mounting pole through the
wireway in the top cover and then thread/screw the top cover onto the
mounting pole until tight (and in desired orientation).
3.
Tighten set screw location on cast top to prevent fixture rotation.
4.
Follow steps 4 through 10 from previous section of instructions.