Hubbell CIRCUIT-LOCK Series Скачать руководство пользователя страница 2

PD1788   

(SHEET 1 of 3 • PAGE 2)

PRINTED IN U.S.A.         8/06

CAT. NOS.

AMPS

RATING

HORSEPOWER

USE PIN & SLEEVE

WIRE

[kW]

PLUG CAT. NO.

PER FIG.

HBL330MI4W

30

120VAC

2  [1.5]

HBL330P4W

W1

HBL330MI6W

30

240VAC

3  (208-240VAC)   [2.25]

HBL330P6W

W2

HBL330MI7W

30

480VAC

7.5  [5.62]

HBL330P7W

W2

HBL430MI5W

30

600VAC 3Ø

20  [15]

HBL430P5W

W3

HBL430MI7W

30

480VAC 3Ø

15  [11.25]

HBL430P7W

W3

HBL430MI9W

30

240VAC 3Ø

7.5  [5.62]

HBL430P9W

W3

HBL430MI12W

30

120 / 240VAC

3  (208-240VAC, L-L)  [2.25]

HBL430P12W

W4

HBL432MI3W

32

380VAC 3Ø 50 Hz

15  (440VAC 3 Ø 60 Hz) [11.25]

HBL432P3W

W3

440VAC 3Ø 60Hz

HBL530MI5W

30

347 / 600VAC 3ØY

20  [15]

HBL530P5W

W5

HBL530MI7W

30

277 / 480VAC 3ØY

15  [11.25]

HBL530P7W

W5

HBL530MI9W

30

120 / 208VAC 3ØY

5  [3.75]

HBL530P9W

W5

HBL360MI4W

60

120VAC

3  [1.5]

HBL360P4W

W1

HBL360MI6W

60

240VAC

7.5  (208-240VAC)  [5.62]

HBL360P6W

W2

HBL360MI7W

60

480VAC

20  [15]

HBL360P7W

W2

HBL

60

600VAC 3Ø

40  [30]

HBL460P5W

W3

HBL460MI7W

60

480VAC 3Ø

30  [22.5]

HBL460P7W

W3

HBL460MI9W

60

240VAC 3Ø

15  [11.25]

HBL460P9W

W3

HBL460MI12W

60

120 / 240VAC

7.5  (208-240VAC, L-L)  [5.62]

HBL460P12W

W4

HBL560MI5W

60

347 / 600VAC 3ØY

40  [30]

HBL560P5W

W5

HBL560MI7W

60

277 / 480VAC 3ØY

30  [22.5]

HBL560P7W

W5

HBL560MI9W

60

120 / 208VAC 3ØY

15  [11.25]

HBL560P9W

W5

HBL3100MI4W

*

100

120VAC

5  [3.75]

HBL3100P4W

W1

240VAC

15 [11.25]

  HBL3100MI6W

100

208VAC

10  [7.5]

HBL3100P6W

W2

HBL3100MI7W

*

100

480VAC

30  [22.5]

HBL3100P7W

W2

HBL4100MI5W

100

600VAC 3Ø

50  [37.5]

HBL4100P5W

W3

HBL4100MI7W

100

480VAC 3Ø

50  [37.5]

HBL4100P7W

W3

HBL4100MI9W

100

240VAC 3Ø

25  [18.75]

HBL4100P9W

W3

 

 HBL4100MI12W

*

100

120/240VAC

15  [11.25]

HBL4100P12W

W4

208VAC

10 [11.25]

HBL5100MI5W

*

100

347 / 600VAC 3ØY

50  [37.5]

HBL5100P5W

W5

HBL5100MI7W

*

100

277 / 480VAC 3ØY

50  [37.5]

HBL5100P7W

W5

HBL5100MI9W

100

120 / 208VAC 3ØY

20  [15]

HBL5100P9W

W5

L

W G

N

L1

L2 L3

T1

T2 T3

N

GREEN/YELLOW

GROUNDING

(BONDING)

PLATE

GROUND
BUSS
(GRN/YEL)

NEUTRAL
BUSS
(BLUE)

2 POLE 3 WIRE
SINGLE PHASE

FIG. W1

G

G

GROUND
BUSS
(GRN/YEL)

GREEN/YELLOW

L1

L2 L3

T1

T2 T3

2 POLE 3 WIRE
SINGLE PHASE

FIG. W2

GROUNDING

(BONDING)

PLATE

L+

L1

L2

L3

L1

L2 L3

T1

T2 T3

L

L G

X Y Z G

GREEN/YELLOW

GROUND
BUSS
(GRN/YEL)

G

GROUNDING

(BONDING)

PLATE

3 POLE 4 WIRE

3 Ø

FIG. W3

L

L

G

W

N G

L1

L2 L3

T1

T2 T3

NEUTRAL
BUSS
(BLUE)

NEUTRAL
BUSS
(BLUE)

GROUNDING

(BONDING)

PLATE

GROUNDING

(BONDING)

PLATE

GREEN/YELLOW

GREEN/YELLOW

L1

L2

N

3 POLE 4 WIRE

EDISON SYSTEM

FIG. W4

GROUND
BUSS
(GRN/YEL)

N G

L1

L2 L3

T1

T2 T3

L1

L2

L3

N

X Y Z W G

FIG. W5

4 POLE 5 WIRE

3 Ø Y

B. Wiring Instructions

1. Select conductors having 90°C or higher rated insulation and sufficient ampacity in accordance

with the 60°C column (for 30 Amp and  60 Amp devices) or the 75ºC column (for 100 Amp
devices) of the National Electrical Code

®

 Table 310-16 or Canadian Electrical Code Table 2.

2.

CAUTION

: USE COPPER CONDUCTORS ONLY.

3. DO NOT TIN CONDUCTORS.
4. Make sure the connected equipment rating does not exceed the rating of this device. See

General Information #4 regarding overcurrent protection.

5. Terminal capacity as indicated in Table 1
6. Strip conductor insulation ½ inch (13 mm).
7. Select proper wiring diagram. Loosen terminal screws. Insert conductors fully into proper terminal.
8. Tighten terminal screws to torque indicated in Table 2:
9.

TAKE CAUTION THAT THERE ARE NO STRAY WIRE STRANDS.

10. Tighten the grounding buss mounting screw to 10-12 lb•in (1.2-1.4 N•m).
11. Reinstall the cover. The handle must be in the 

OFF

 position. Make sure the rope gasket is

properly seated in the groove. Tighten the four cover screws to 10-12 lb•in (1.2-1.4 N•m).

12. Consult factory for auxiliary contact availability.

INSTALLATION INSTRUCTIONS

   

(CONTINUED)

30 AMP

60 & 100 AMP

FIG. M4 • BACK FEED

(TYPE 4X INSTALLATIONS ONLY)

GROUNDING

(BONDING)

PLATE

MOLDED IN DRILL POINT
(ONE TOP, ONE BACK,
ONE BOTTOM)

FIG. M3 • TOP FEED

30 AMP

60 & 100 AMP

GROUND
BUSS
(GRN/YEL)

PROVIDE

CONDENSATE

DRIP LOOP

AS SHOWN

THIS DEVICE CARRIES A MAXIMUM RATING OF:

G

G

G

G

G

WIRING DIAGRAMS

Consult factory for availability

30A

60A

100A

Switch

#4 to #12 AWG

#2 to #10 AWG

#2 to #10 AWG

Ground

#6 to #16 AWG

#4 to #10 AWG

#4 to #10 AWG

Neutral

#8 to #22 AWG

#4 to #14 AWG

#1/0 to #14 AWG

Auxiliary

contact

#14-18 AWG

#14-18 AWG

#14-18 AWG

TABLE 1

30A

60 & 100A

Switch

27  lb•in (3.0 N•m)

50 lb•in (5.7 N•m)

Ground

16-18 lb•in (1.8-2.0 N•m)

22 lb•in (2.5 N•m)

Neutral

13-15 lb•in (1.5-1.7 N•m)

22 lb•in (2.5 N•m)

Auxiliary

10-12 lb•in (1.2-1.4 N•m)

10-12 lb•in (1.2-1.4 N•m)

contact

TABLE 2

Pilot

                                                20 lb-in (2.5 N•m)

Pilot

#12-18 AWG

P12-18 AWG

Pilot contact (if installed)