©2017 Hubbell Incorporated | Chance
®
Full Range ARVI Operating Instructions
Specifications
Weight (w/o batteries):
558 g (23.2 oz)
Dimensions:
12.55" L X 5.15" W X 5.06" H
Battery requirements:
Two (2) Alkaline or Lithium “AA” batteries
Adjustable audible alarm:
92
±
5 dB(A) at 24 inches (61 cm), at 25°C
Operating voltage range(s):
Capacitive Test Point to 765 kV AC (Phase-to-Phase equivalent), 50/60 Hz
Operating temperature range:
-20° to +80°C
Operating humidity range:
5% to 95% Rh
Storage temperature:
-20° to +60°C (Recommended storage at 21°C +/- 2%°C)
Storage humidity range:
5% to 95% Rh (Recommended storage at 45% Rh +/- 8% Rh)
Shock Testing:
per IEC 60068-2-27, "Test Ea and guidance: Shock"
Level 1 - 500 m/s
2
(50g), 11ms Half-sine pulse, 3 pulses Positive & Negative, each axis.
Level 2 - 1000 m/s
2
(100 g
±
4 g), 1.5 to 2.5ms Half-sine pulse, 3 pulses Positive & Negative, each axis
Vibration Testing:
per IEC 60068-2-6, "Test Fc: Vibration (sinusoidal)"
1.5 mm p-p from 10 Hz to 40 Hz, 5g rms from 40 Hz to 2000 Hz for 3.3 hrs each axis
Limitations:
Do not use if damaged or malfunctioning. Always use appropriate length insulated Hot
Sticks even when wearing rubber gloves. To verify proper operation, always test the unit on a known
energized voltage source or with the Voltage Indicator Tester to verify proper operation.