    Chart 

  | 

 Chart 

         | 

 

 

 

 

 

|  The Maximum Voltage across the man  

 

 

 

 

 

   will be limited to 100V AC if the maximum

 99.5% of Workers Will Not Experience Heart   

   jumper resistance is limited to the value

 Fibrillation At Currents & Durations Below:   

|  associated with the selected maximum

   (Based Upon C.F. Dalziel’s Research) 

 

|  fault current available

---------------------------------------------------------------------     --------------------------------------

Assume: 

154 Lb. Man @ 1,000 ohm resistance 

Maximum 

Rj 

 

 

 

 

 

 

Ifault 

Maximum 

 

 

 

 

 

(Amp.) 

(Milliohm) 

       | 

 

 

Maximum Jumper Resistance 

2000  

50.0  

time 

Iman 

 

(mohm) @  

4000  

25.0  

(cycles) 

(mA) 

  Available Fault Current 

6000  

16.7  

 

 

--------------------------------- 

8000  

12.5  

 

 

1000  

5000  

10000  

10000  

10.0  

       | 

12000 

 8.3 

 

2  

860  

861  

172  

86  

14000  

7.1  

3  

702  

703  

140  

70  

16000  

6.3  

4  

608  

608  

122  

61  

18000  

5.6  

5  

544  

544  

109  

54  

20000  

5.0  

6  

496  

497  

99  

50  

22000  

4.5  

7  

460  

460  

92  

46  

24000  

4.2  

8  

430  

430  

86  

43  

26000  

3.8  

9  

405  

406  

81  

41  

28000  

3.6  

10  

385  

385  

77  

38  

30000  

3.3  

11  

367  

367  

73  

37  

32000  

3.1  

12  

351  

351  

70  

35  

34000  

2.9  

13  

337  

337  

67  

34  

36000  

2.8  

14  

325  

325  

65  

33  

38000  

2.6  

15  

314  

314  

63  

31  

40000  

2.5  

16  

304  

304  

61  

30  

17  

295  

295  

59  

29  

18  

287  

287  

57  

29  

19  

279  

279  

56  

28  

20  

272  

272  

54  

27  

21  

265  

265  

53  

27  

22  

259  

259  

52  

26  

23  

254  

254  

51  

25  

24  

248  

248  

50  

25  

25  

243  

243  

49  

24  

26  

239  

239  

48  

24  

27  

234  

234  

47  

23  

28  

230  

230  

46  

23  

29  

226  

226  

45  

23  

30  

222  

222  

44  

22  

Содержание CHANCE C403-3220

Страница 1: ...countered which are not sufficiently covered in this guide contact A B Chance Company NOTE Because Hubbell has a policy of continuous product improvement we reserve the right to change design and spec...

Страница 2: ...3 SELF TEST PROCEDURE 6 THRESHOLD PROGRAMMING 7 1 Threshold Derivation 7 2 Changing the Threshold 8 TEST SETUP 9 GROUND SET TEST PROCEDURE 10 GROUND SET TROUBLESHOOTING WITH PROBES 11 EXPECTED GROUND...

Страница 3: ...Thoroughly read and understand these instructions before using the Tester 3 Fixed Input Connections When the INPUT SELECT switch is in the fixed position The resistance measurement shown will be the...

Страница 4: ...pply 13 Probe Input When the INPUT SELECT switch is in the PROBE position the resistance measurement shown will be the value of resistance between probe contact points 14 Input Select Switch Allows se...

Страница 5: ...Page 5 of 20 P403 3222 Rev K 4 18 Figure 1 Front Panel of Protective Ground Set Tester Showing Feature Location...

Страница 6: ...SELECT switch in the FIXED position 6 Place the CONTINUOUS TEST switch in the OFF position 7 Press the SINGLE TEST switch 8 The display will show the measured resistance of the self test cable on line...

Страница 7: ...utility MUST select actual work site values for system fault cur rent fault duration and permissible maximum worker body current before attempting to set grounding jumper acceptable limits to assure...

Страница 8: ...be the voltage across the man used to calculate the maximum values for the thresholds This voltage can be adjusted using the CABLE SIZE and the CONTINUOUS TEST switches as described in 5 7 5 Select a...

Страница 9: ...rrent from one fixed input to the other during testing Without the ground set the resulting open circuit prevents the resistance measurement If the ground set is left unconnected and the INPUT SELECT...

Страница 10: ...displayed at the end of the first line of the display 6 Place the INPUT SELECT in the FIXED position 7 Place the CONTINUOUS TEST switch in the OFF position 8 Press the SINGLE TEST switch 9 The display...

Страница 11: ...end 9 The display will show the measured resistance from one probe to the other when contacting the ground set on line 2 of the display in m The red light will illuminate if the ground set resistance...

Страница 12: ...maximum resistance value for protective grounds issued to workers for use in a predefined area For example a nearly equipotential zone can be created by placing a protective ground in parallel with th...

Страница 13: ...ce for a given set of conditions Rj Rm Im If Im Eq 3 Example 1 Assume Rm 1 000 ohmsK 157 If 1 000 Amp t 25 Sec Imax 314 milliamperes fibrillation threshold from Eq 1 With 3 1 safety margin Rj 100 mill...

Страница 14: ...and Graph 1 This chart is based upon C F Dalziel s research and widely used industry values Calculations were made using equation 1 with the variable being time duration of current flow Chart 2 and Gr...

Страница 15: ...tions vol 79 part III 1960 pp 667 673 6 Dalziel C F Massoglia F P LET GO CURRENTS AND VOLT VOLTAGES AIEE Transactions vol 75 part II 1956 pp 49 56 7 Dalziel C F ELECTRIC SHOCK HAZARD IEEE Spectrum Feb...

Страница 16: ...k up breakers maximum operation time 20 cycles 333 sec Utility s Accepted level of safety Vworker max 100 Volts Iworker max 0 100 ampere 100 milliampere from Eq 4 Maximum parallel jumper resistance al...

Страница 17: ...ble Fault Current 6000 16 7 8000 12 5 1000 5000 10000 10000 10 0 12000 8 3 2 860 861 172 86 14000 7 1 3 702 703 140 70 16000 6 3 4 608 608 122 61 18000 5 6 5 544 544 109 54 20000 5 0 6 496 497 99 50 2...

Страница 18: ...alziel s Equation Time cycles Resistance milliohms 700 600 500 400 300 200 100 5 10 15 20 25 30 Graph 1 This chart is based upon C F Dalziel s research and widely used industry values Calculations wer...

Страница 19: ...0 V Max Resistance milliohms Graph 2 This chart represents the maximum allowable resistance of the protective ground based upon the constraint that the maximum voltage drop across the man will never e...

Страница 20: ...20 of 20 P403 3222 Rev K 4 18 Hubbell Chance USA 210 N Allen Street Centralia Mo 65240 1395 573 682 5521 Fax 573 682 8475 Copyright 2016 Hubbell Incorporated 210 N Allen Centralia MO 65240 Printed in...

Отзывы: