MP15 Jockey Pump Controller 

9

 

 

 

Publication 245-EN – November 2013 

 

User Log In 

Navigating and viewing set point configurations is allowed at all times; 

however, changing any set point configuration requires the user password. The 

user password is shown below. This password is also on a label affixed to the 

cabinet door on the inside. 
When prompted for the user password, enter the following button sequence: 

E N T E R

 — 

U P

 — 

D O W N

 — 

D O W N

 — 

D O W N  

                              (1)          (2)           (3)             (3)            (3) 

Logging Out 

If there is no user activity on the OID after five minutes, the login state is 

automatically logged out. 

To manually log out: 

 

From the Home window, choose 

Log Out

Note

: The 

Log Out

 menu item will not be displayed if the current user login 

status is not logged in. 

 

Configuring System Set Points 

WARNING 

To configure the system set points, place the HOA 
Selector in the Off position. 

 

WARNING 

Adjustments should be performed by qualified 
personnel only. 

 
Configuring a set point value consists of one or more steps, depending on the set 

point.  Use the 

U

P

 and 

D

O W N

 buttons to change the value of the current step.  

Press the 

E

N T E R

 button to confirm the value of the current step. Once the last step 

has been complete, the set point value will be saved. 
For example, the 

Start Pressure

 set point has three steps.  The first step adjusts 

the hundredths column, the second step adjusts the tenths column, and the third 

step adjusts the ones column. 

Содержание Metron MP15

Страница 1: ...ration maintenance and system setup information for Metron Model MP15 Jockey Pump Controllers Section Page Introduction 2 Installation 3 Operation of the Controller 5 Operator Interface Device OID Use...

Страница 2: ...ormal water pressure and prevent unnecessary cycling of the main fire pump s Approvals Metron MP15 controllers are listed by Underwriter s Laboratories Inc in accordance with UL508A Standard for Indus...

Страница 3: ...d risk of SERIOUS INJURY or DEATH and to avoid damage to the controller READ THIS SECTION CAREFULLY If questions or concerns still exist contact the Metron factory for further clarification If work mu...

Страница 4: ...he installer is responsible for ensuring no metallic foreign objects such as drilling chips etc fall inside the controller onto the electrical circuit Failure to observe this could result in damage to...

Страница 5: ...may fluctuate slightly due to small leaks in the system The use of this small pump will eliminate frequent starting of the main pump The Jockey Pump Controller automatically starts the Jockey Pump Mo...

Страница 6: ...erly installed all external connections have been made and the Motor Starter Protector is closed Manual Operation To manually start the jockey pump motor turn the HOA Selector to the Hand position Thi...

Страница 7: ...ist of windows They are denoted onscreen with an arrow to the right of the text Set Points which display the set point name and its current value Use the EN T E R UP and DO WN buttons to navigate thro...

Страница 8: ...sure HOA switch position and status of the pump If there is no user activity on the OID after five minutes the onscreen window will automatically return to the Home window Alarms and Events When there...

Страница 9: ...ndow choose Log Out Note The Log Out menu item will not be displayed if the current user login status is not logged in Configuring System Set Points WARNING To configure the system set points place th...

Страница 10: ...the UP and DO WN buttons to change the value of the current step b Use the EN T E R button to confirm with current step 3 When the current set point configuration is complete the next set point will...

Страница 11: ...igation Tree Home Window System Set Points User Preferences Tech Screen USB Memory Stick About Window Calibrate Pressure Sensor Language Pressure Unit Screen Brightness Start Pressure Stop Pressure St...

Страница 12: ...automatic start of the pump when a low system pressure condition occurs Range 0 999 Seconds Minimum Run Time The minimum time that the pump must run before an automatic stop Range 0 999 Seconds Short...

Страница 13: ...mber 2013 Set Point Definition Language Selects the onscreen language Pressure Unit Selects the system pressure unit PSI or BAR Screen Brightness Adjusts the brightness of the screen backlight Calibra...

Страница 14: ...Pump Running LED should turn on 3 Turn the HOA switch to the Off position 4 The pump should stop immediately and the Pump Running LED should turn off Automatic Pressure Start 1 Turn the HOA switch to...

Страница 15: ...g manual or automatic Pump Stopped The pump has stopped running manual or automatic Pressure Sensor Fault A pressure sensor fault alarm has occurred HOA Switch Fault An HOA Switch fault alarm has occu...

Страница 16: ...t regulations which is applicable in all EC countries At the end of the service life of the equipment the company offers to collect and dispose of this equipment in accordance with regulations in forc...

Страница 17: ...21 Publication 245 EN November 2013 Printed in USA Replacement Parts For replacement parts contact your local Metron sales office or the Metron factory at United States Telephone 1 336 434 2800 FAX 1...

Отзывы: