1. DIRECTIONS FOR INSTALLATION

CAUTION: 

Before beginning installation, make 

sure that the supplying circuit is turn 

OFF.

Be sure the flame paths (cover to box mating 

surfaces and threaded openings) do not become 

damaged.

Do not install in a corrosive area which will 

attack the “copper free” aluminium alloys or 

stainless steel shaft unless the casting and 

parts have been protected against the specific 

corrosive environment.

Do not locate in areas where dust, ice, snow, 

or other substance will accumulate and thereby 

impair the rotary operation of the device.

XCS-0S device are for surface mounting in 

hazardous atmospheres as defined by NEC 

article 500. They contain an electrical device 

and must be sealed from the conduit system as 

required by article 501-5. Type “ENY”, “EY” or 

“EYS” series (or equivalent).

Install sealing fitting as required in class l & ll 

areas. 

(Note

: For class l (5) and class ll(3-1/2) full 

threads engagement are required).
The conduit threads should be lubricated with a 

non-electrical insulating lubricant, or pipe joint 

compound which will not promote corrosion or 

chemically attack aluminium.

After the conduit system has been properly 

installed, pull the wires and make the electrical 

connections as required.

The electrical circuits and ground continuity 

should be checked with an instrument approved 

for the area.

Flame Path machined on cover & box  such that 

a 0.0015”  Feeler gauge will not enter more than 

1/8” when fully assembled  & bolted to box. Care 

must be taken that surface is not damaged.

2. OPERATION

The mechanical action of these devices is 

rotary.The electrical action is dependent 

upon the cam configuration and the 

contact block used. (See chart). An  

accessory locking device may be used 

with the standard selector switch without 

alternations.

3. MAINTENANCE 

The Shaft should be lubricated 

occasionally to prevent binding. Use 

Killark “LUBG” (general purpose ) or Killark 

“LUBT” (high temperature) lubricants.