INSTALLATION, OPERATION & 

MAINTENANCE DATA SHEET 

SERIES ECF, EKJ, EKJSS Flexible Fittings 

 For Use In Classified Hazardous Locations

 

 

2.  Installation Instructions:

 

 

Apply a non-hardening lubrication to the threads on both ends of the 
flexible fitting.  Killark’s thread lubricate “LUBG or LUBT” is 
recommended.  Other certified  lubrications or petroleum jelly may be 
used.  
 
Thread one end of the flexible fitting into the correct size NPT female 
opening or male nipple until hand tight plus one turn minimum with a 
wrench. At this point the flexible fitting will no longer be able to be turned.  
The opposite end will require a certified union or un-poured sealing fitting 
threaded onto it, again, until hand tight plus one turn minimum with a 
wrench.  
 
When installing the flexible fitting ensure that all bends are not less than 
the minimum bend radius allowed.  Refer to the catalog for the radii of 
the flexible fittings.   

 

Minimum Bend Radius 

 

Series 

         Conduit Size (inches) 
1/2  3/4  1 

1-1/4 

1-1/2 

ECF 

10”  12”  14”  ----  ----  ---- 

EKJ 

10”  12”  14”  14”  16”  18” 

 

 

 
3.  Certification Information:

 

 

UL  Certifications: 

Refer to the Killark Catalog for North American “Class and Division” 
ratings as they vary by Series and Conduit Size. 

IEC / ATEX Certifications: 

IECEx SIR 10.0057U Iss. 2   /   Sira 10ATEX 1068U  Iss. 3 

0539

 II 2 GD   

Ex de IIC Gb       
Ex tb IIIC Db  

 

Standards Applied: 
EN 60079-0:2012+A11:2013          IEC 60079-0:2011 Ed. 6.0 
EN 60079-31: 2014                        IEC 60079-31:2013

t

 Ed. 2 

EN 60079-1: 2014                          IEC 60079-1:2014-06 Ed. 7 

 

CONDITIONS FOR SAFE USE: 

 
1.    

Each Flexible Fitting Series EKJ-EX, ECF-EX and EKJSS-EX 

conduit assembly shall be provided with a suitably certified conduit 
sealing device at the point where it connects to the associated 
flameproof equipment.  
 
2.    Each Flexible Fitting Series EKJ-EX, ECF-EX and EKJSS-EX 
conduit assembly is capable of meeting a degree of ingress protection of 
IP66. This condition will only be met when the ends are connected to a 
certified conduit sealing device or fitting which is rated IP66.  
 
3.    The temperature range in which the Flexible Fitting Series may be 
used is limited to -40°C to 150°C. Caution: If using conductors with a 
lower temperature range the temperature rating of the assembly defaults 
to that of the conductors.   
  
4.    The user shall ensure the appropriate earthing / grounding method 
is provided for the conduit assembly.

 

 

P/N KIL00921480  FORM NO. K1480 ERO-8-049-16  Page 2 of 3 

 

 