pipe and the regulating valve on the comprehensive tester. Remove the adapter

from the SF6 electrical equipment. If you need to continue measuring other

equipment, please do not turn off the power ,follow the steps above to make the

next measurement.

7. After the measurement is finished, turn off the power.

IV.Menu Operation

In the measurement state, the function menu can be accessed by the OK button, as

shown in Figure 1.

1.Save The Data

In the measurement state, press the “OK” button to enter the function menu, press

the “Up” and “Down” buttons to select the “Save Record” menu, and press the “OK” button

to enter the Save Data page. When saving the data, you can perform the data according

to the device. Numbering.

The device number can be up to five digits. You can increase the value by using the

“up” and “down” keys, and the “left” and “right” keys to adjust the number of data digits.

After entering the number, press the “OK” button to save the data and return to the

measurement page automatically. Press the “Cancel” button to return to the function

Содержание HZSF-641

Страница 1: ...HZSF 641 SF6 Gas Analyzer Huazheng Electric Manufacturing Baoding Co Ltd...

Страница 2: ......

Страница 3: ...can work continuously for more than 10 hours when fully charged When the integrated tester is left unused for a long time some air will remain in the test pipe and air chamber In the first test the h...

Страница 4: ...Contents I Technical Characteristics And Parameters 1 II Panel Instruction 3 III Measurement 4 IV Menu Operation 5 V Remarks 8 VI Packing List 9...

Страница 5: ......

Страница 6: ...gas saving After the start up into the measurement state the measurement time per SF6 gas dew point is about 5 minutes and the measurement time of SF6 purity and SF6 decomposition product is about 2 m...

Страница 7: ...uing Range 0 100ppm Minimum detection 0 1ppm accuracy 0 5 stability 0 100ppm Repeatability 2 SO2 Measuring range 0 100ppm Minimum detection 0 1ppm accuracy 0 5 stability 0 100ppm Repeatability 2 Ambie...

Страница 8: ...The angle of the bracket can be adjusted by simultaneously pressing the bracket adjustment buttons on both sides 2 Rear Panel Flow meter LCD Key button Gas inlet Charging indicator Power switch RS232...

Страница 9: ...in the upper right corner If the battery level is lower than about 20 please turn off and charge it 4 Start Measuring After the instrument completes the initialization and self checking it automatica...

Страница 10: ...ure 1 1 Save The Data In the measurement state press the OK button to enter the function menu press the Up and Down buttons to select the Save Record menu and press the OK button to enter the Save Dat...

Страница 11: ...the Up and Down buttons to select the modification time and press the OK button to enter the modification time page At this time the year month day and time can be modified And points the method is a...

Страница 12: ...bination Use This Function Is Limited To Dedicated Operation Press the OK button on the measurement interface to enter the function menu Press the Down button once When the second item is selected pre...

Страница 13: ...is not in use it should be placed in an aluminum alloy packaging box and placed on the test bench or instrument rack to prevent dust and moisture 4 The instrument is calibrated once a year with standa...

Страница 14: ...9 VI Packing List No Item Qty 1 Main engine 1 2 Gas Inlet pipe 1 3 Gas outlet pipe 1 4 Power line 1...