4
3.2.1 Three-phase power input aviation socket: this socket is connected to aviation
socket of voltage regulator 380V power output end.
3.2.2 Power indicator: Used to indicate whether the three-phase power supply is normal.
3.2.3 Input socket of voltage regulator: This socket is connected to output end of voltage
regulator 0 ~ 430V.
3.2.4 Output indicator light of the voltage regulator: It is used to indicate the output
voltage of the voltage regulator. When the output voltage of the voltage regulator is lower
than 60V, the light will not turn on.
3.2.5 Large current output terminals: This group of terminals outputs large three-phase
AC current, which is 0 ~ 300A/ phase, and the port voltage is 15V/ phase.
3.2.6 Three-phase voltage output terminals: This set of terminals outputs three-phase AC
voltage, which is 58V/ phase and the maximum output current is 3A/ phase.
3.2.7 Grounding terminal: The terminal shall be grounded with a special wire for safety.
3.2.8 Cut out button: Press this button to cut out the three-phase voltage and put out the
indicator light of the output button.
3.2.9 Output button: Press this button, three-phase voltage is output, and the button
indicator is on.
3.2.10 LCD: display current and voltage values.
3.2.11 Serial port can be connected to PC for program update.
3.2.12 LCD display adjustment: Used to adjust the backlight of the LCD screen.