8 Commissioning Core Components
Issue 02 (2019-12-20)
Copyright © Huawei Technologies Co., Ltd.
66
Figure 8-6
Teamwork topology
Table 8-6
Notes for the screen
No. Parameters Note
1
On/Off
On
indicates that the smart cooling product is started and
Off
indicates that the smart cooling product is shut down.
2
01, 02, 03
Indicates the device address. The minimum address is the master
one and the rest are all slave ones.
NOTE
If the master one offline, the online device with the smallest address is
selected to be the new master.
3
Active/Stand
by
Active: properly responds to the requirement control.
Standby: responds to the requirement control when active one is
faulty (critical alarms, shutdown, and offline) or cannot meet
cooling requirements.
4
M/S
M indicates the master unit, and S indicates a slave unit. Blue
indicates that the device is operating, and gray indicates that the
device is idle.
5
Frame:
green/non-gr
een
A device with green frame indicates the device itself,
as shown in
.
A non-green frame indicates the other device in the group,
as shown in
.
6
Ground
color: red,
bright gray
Red indicates that a critical alarm is generated,
as shown in
.
Bright gray indicates that the device is operating without any