Advanced Cooling Controller
User Manual
4 Maintenance Guide
Issue Draft A (2014-12-26)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
44
Figure 4-21
Screen displayed when the calibration is complete
Calibrating the screen by DIP switch.
1.
Flip toggle switch 1 for the LCD to ON, and others to the opposite position, and wait for
3 seconds before calibrating.
shows the toggle switches for the screen.
2.
Flip the fourth toggle switch to ON and others remain unchanged, the screen calibration
function is triggered.
After 15 seconds, a dialog box indicating
Are you sure you want to calibrate the
screen? If you do not click Yes or No, calibration will start automatically 10 seconds
later.
is displayed, as shown in
Figure 4-22
Confirming to calibrate the screen
3.
Wait for 10s or tap
Yes
is displayed. Tap the screen. When
displayed, the adjustment is complete.
4.
Flip toggle switch 1 for the LCD to ON, and others to the opposite position.
You need to manually operate the operation again from
to trigger the touchscreen calibration
function after the calibration failure.
----End