Figure 3-13 Installing conversion brackets (four-cabinet 800 kVA model)
Step 4 Remove the side panels from the top air-flow cabinets.
●
For a dual-cabinet UPS, remove the side panel between top air-flow cabinets
1 and 2.
Figure 3-14 Installation positions of the top air-flow cabinets for a dual-
cabinet UPS
●
For a four-cabinet UPS, remove the left and right side panels of top air-flow
cabinets 2 and 3, left side panel of top air-flow cabinet 1, and right side panel
of top air-flow cabinet 4.
Figure 3-15 Installation positions of the top air-flow cabinets for a four-cabinet
UPS
UPS5000 Top Air-flow Cabinet
User Manual
3 Product Installation
Issue 02 (2022-01-19)