If a third-party reliable power supply is used, use the power signal with a
voltage of 240 V AC or less and a current of less than 6 A. (1200 kVA and
1600 kVA UPSs support this feature.)
Figure 6-415 Cable connections between the backfeed protection card and
shunt release
(1) Shunt release (provided by the
customer)
(2) 6 A fuse (provided by the customer)
----End
6.12 Connecting a Remote EPO Switch
NO TICE
● Huawei does not provide the EPO switch or cable. Prepare them by yourself.
The recommended cable size is 0.3 mm
2
.
● Equip the EPO switch with a protective cover to prevent misoperations, and
protect the cable with a protective tube.
● Triggering EPO will shut down the rectifier, inverter, charger, and static bypass,
but will not disconnect the UPS mains input. To power off the UPS completely,
turn off the upstream input switch when you trigger EPO.
Use a cable to connect the EPO switch to the dry contact port on the control
module of the UPS.
UPS5000-H-(1200 kVA-1600 kVA)
User Manual (100 kVA Power Modules)
6 Installation
Issue 05 (2021-10-13)
Copyright © Huawei Technologies Co., Ltd.
321