Figure 6-404 Installing mounting plates
6.7 Parallel System Installation
Prerequisites
NO TICE
● The length and specifications of power cables on each UPS should be the same
to achieve current equalization in bypass mode. The power cables include
bypass input power cables and UPS output power cables.
● Ensure that the phase sequences of the mains input, bypass input, and output
power cables of each UPS are the same.
● Connect power cables according to port silk screens.
Procedure
Step 1 Ground each UPS in a parallel system separately, and connect power cables and
battery cables.
Step 2 Choose a parallel mode and connect power cables to the parallel system based on
site requirements.
The typical scenario of a 1+1 parallel system is used as an example.
UPS5000-H-(1200 kVA-1600 kVA)
User Manual (100 kVA Power Modules)
6 Installation
Issue 05 (2021-10-13)