Huawei UPS5000-H-400K-NTN Скачать руководство пользователя страница 4

Signal cable hole

Power cable hole

Signal cable 
routing from the 
inductor cabinet to 
the UPS cabinet

Equipotential 
ground point

4

03

Verifying the Installation

UPS5000-H-400 kVA & 800 kVA-NTN Quick Guide (Singapore 1-NET, 100 kVA Power Modules)

Installing Rectifiers and Cables (800 kVA)

Different power sources

Single power source

1. Check that there is no foreign matter in the cabinets.
2. (Remove the paper protective film from the sealing putty.) After routing cables and verifying cable connections, seal the gap between cables and the cabinet using sealing putty.
3. After verifying the installation, reinstall all the covers.
4. Do not remove the dustproof cover before power-on to prevent dust from entering the UPS.

Cables have been preinstalled and bound in the inductor cabinet.

The number and colors of cables in the figures are for reference only.

Do not bind signal cables and power cables together.

Signal cable hole

Power cable hole

Signal cable route

Signal cable route

Signal cable 
routing from the 
inductor cabinet to 
the UPS cabinet

Equipotential 
ground point

Содержание UPS5000-H-400K-NTN

Страница 1: ...al injury or equipment damage may occur and the resulting UPS faults are beyond the warranty scope of Huawei 4 This document describes the installation procedure for a single UPS For details about how to install a parallel system contact Huawei technical support Model Weight Dimensions H x W x D UPS5000 H 400K NTN UPS cabinet 800 kg Inductor cabinet 550 kg UPS cabinet 2000 mm x 800 mm x 1000 mm In...

Страница 2: ... 100 kVA Power Modules M12 bolt Spring washer Flat washer Expansion sleeve Expansion nut Concrete floor Cabinet Description Unpacking Securing the Cabinet Space planning Bypass input Control module Main switch QF of the inductor cabinet Rectifiers UPS cabinet Inductor cabinet Inductor cabinet UPS cabinet Bypass modules PSU for fans ...

Страница 3: ... in the figures are for reference only Do not bind signal cables and power cables together UPS5000 H 400 kVA 800 kVA NTN Quick Guide Singapore 1 NET 100 kVA Power Modules Different power sources Single power source Equipotential ground point Signal cable hole Power cable hole Signal cable route outside the cabinets Signal cable route outside the cabinets Signal cable routing from the inductor cabi...

Страница 4: ...ling putty After routing cables and verifying cable connections seal the gap between cables and the cabinet using sealing putty 3 After verifying the installation reinstall all the covers 4 Do not remove the dustproof cover before power on to prevent dust from entering the UPS Cables have been preinstalled and bound in the inductor cabinet The number and colors of cables in the figures are for ref...

Страница 5: ...code and Verification code obtained from the LCD on the Offline Activation screen Tap Generate PWD to generate a startup password Set Site and Device Type as required and tap Offline Activation Enter the generated password in the password text box on the LCD to start the UPS Use the app to start the UPS online Yes No start the UPS offline On the app home screen tap StartUp to access the Set Startu...