Reserve a clearance of at least 950 mm from the front of the cabinet for
ventilation and operations.
●
Reserve a clearance of at least 500 mm from the top of the cabinet for
operations.
●
Reserve a clearance of at least 500 mm from the rear of the cabinet for
ventilation.
●
Reserve a clearance of at least 800 mm if you need to perform operations at
the rear of the cabinet.