4.5 Setting ECO Mode
Prerequisites
The system is working in inverter mode.
Context
●
The UPS is set to non-ECO mode by default. Set the UPS to ECO mode when
energy saving is required.
●
In ECO mode, the bypass takes priority over the inverter in supplying power. If
the bypass fails, the UPS transfers to inverter mode.
●
Both a single UPS and the parallel system support the ECO mode for higher
efficiency.
●
To avoid frequent transfer between ECO mode and normal mode, do not set
the ECO mode when the bypass input is unstable or is sensitive to load
changes.
●
ECO mode is not recommended when the load is less than 10%.
●
Before setting ECO mode, ensure that the bypass is working properly.
Procedure
Step 1 On the LCD, choose System Info > Settings > System Settings and set Working
mode to ECO. The information indicating that the UPS works in ECO mode is
displayed on the LCD.
Step 2 Set the ECO voltage range.
Figure 4-6 ECO parameters
Step 3 (Optional) If you set ECO mode in bypass mode, manually start the UPS inverter.