5.6 Testing Batteries
5.6.1 Forced Equalized Charging Test
Context
Before a forced equalized charging test, ensure that:
The mains input is normal.
Batteries are properly connected.
Batteries are not in the equalized charging state.
Procedure
Step 1
On the home screen of the LCD, choose
System Info
>
Maintenance
>
Battery Maint
.
Step 2
Tap
Start
next to
Forced Equalized Charging
to start a forced equalized charging test.