UPS2000-G-(3 kVA-20 kVA)-V2
User Manual (Two Live Wires)
4 Control Panel
Issue 07 (2019-12-19)
Copyright © Huawei Technologies Co., Ltd.
57
Figure 4-18
Parallel-System Load screen
N+X Parallel-System
screen
A parallel system is running. X (value range: 0–3) indicates the number of redundant
UPSs (configurable on the LCD); N (value range: 1–4) indicates the number of requisite
UPSs (total number of UPSs minus X). The total number of UPSs is automatically
identified by the system.
Sys. Sout
parameter
System phase A, B, and C apparent power displayed on the
Parallel-System Load
screen. The parameter is
Sys. Sout_A, Sys. Sout_ B
, and
Sys. Sout_C
in the case of
three-phase input; the parameters are not displayed in single UPS mode.
Sys. Pout
parameter
System phase A, B, and C active power displayed on the
Parallel-System Load
screen.
The parameter is
Sys. Pout_A, Sys. Pout_ B
, and
Sys. Pout_C
in the case of three-phase
input; the parameters are not displayed in single UPS mode.
Sys. Load ratio
parameter
System phase A, B, and C load ratio displayed on the
Parallel-System Load
screen. The
parameter is
Sys. Load ratio_A, Sys. Load ratio_B
, and
Sys. Load ratio_C
in the case
of three-phase input, and the parameters are not displayed in single UPS mode.
System information is not displayed in single UPS mode.
Environment Monitoring Screen
Environment Monitoring
screen.
Figure 4-19
Environment Monitoring screen
Ambient temp.
parameter
Temperature detected by the ambient temperature and humidity sensor (used together
with an SNMP card; if the sensor is not connected,
NA
is displayed.)
Ambient humidity
parameter
Temperature and humidity sensor humidity (Install an SNMP card and a temperature and
humidity sensor; if they are not installed, NA is displayed.)
Internal temp.
parameter