UPS2000-G-(3 kVA-20 kVA)-V2
User Manual (Two Live Wires)
3 Installation
Issue 07 (2019-12-19)
Copyright © Huawei Technologies Co., Ltd.
37
Model
Wiring
Termin
al
Numb
er of
Phases
Rated
Voltage
External
Circuit
Breaker
Cross-s
ectional
Area
Termin
al Type
Torqu
e for
Tighte
ning
Bolts
Output
3
380 V
AC, 400
V AC, or
415 V
AC
63 A (the
characteri
stics of D)
10 mm
2
10 mm
2
M6 OT
terminal
2.8 N
m
If customers purchase input and output power cables by themselves, use the cables that comply with
standards proposed by Underwriters Laboratories (UL) or International Electrotechnical
Commission (IEC).
Two-mains-input scenarios are not supported on the UPS2000-G-15 kVA/20 kVA (single-phase
input single-phase output).
3.1.4 Unpacking and Checking
shows the transportation safety requirements.
Figure 3-4
Transportation safety requirements
Only trained personnel are allowed to move the UPS.
Do not move the UPS by holding its mounting ears, front panel, terminal cover, or
monitoring module.
At least two persons are required to move the battery pack and transformer because they
are heavy. Exercise caution when moving them. Prevent the battery pack from falling over;
otherwise, fire accidents may occur. Remove rings, watches, and other metal objects when
you move the battery pack.
To prevent shocks or falls, move the UPS gently. After placing the UPS in the installation
position, unpack it carefully to prevent scratches.
Procedure
Step 1
Visually inspect the UPS appearance for shipping damage. If any shipping damage is found,
report it to the carrier immediately.