UPS2000-A-(6 kVA-10 kVA)
User Manual
B Alarm Handling
Issue 05 (2019-12-19)
Copyright © Huawei Technologies Co., Ltd.
137
Alarm
Name
Alarm
Identifier
(Alarm ID)
WebUI
Decimal
System
Alarm
Identifier
(Alarm ID)
LCD
Heuristicim
al System
Alarm
level
Alarm
Clear
Mode
Impact on
the System
Repair Proposal
lifespan is
affected.
number of batteries.
Measure: Check that
the configured
number of batteries
is consistent with the
actual number.
Possible cause: The
actual number of
batteries does not
meet requirements.
Measure: Check that
the actual number of
batteries meets
requirements.
Possible cause: The
charger is abnormal.
Measure: Check that
the charger voltage
is normal
immediately after
the batteries are
disconnected.
Remainin
g cap.
warning
22-1
34-1
Minor
Automatic
clear
If no action is
taken,
continued
discharge will
result in
system
shutdown due
to EOD.
Possible cause: The
battery discharge
lasts too long.
Measure: Check the
mains, and charge
batteries in a timely
manner.
Possible cause: The
mains input is
abnormal.
Measure: Check the
mains, and charge
batteries in a timely
manner.
Possible cause: The
number of batteries
or battery capacity is
incorrectly set.
Measure: Check the
configured battery
capacity.