UPS2000-A-(6 kVA-10 kVA)-RTL
User Manual
9 Technical Specifications
Issue 07 (2020-01-10)
Copyright © Huawei Technologies Co., Ltd.
81
Item
6 kVA/10 kVA
For the power backup time of the battery pack
for the 10 kVA UPS, see
Parallel feature
A maximum of four battery strings are connected
in parallel. That is, a maximum of four battery
packs are installed.
Rated charger charge current
2 A by default; 1–12 A configurable, tolerance
±0.5 A
Charger charge time
Determined by the battery capacity.
Rated charger charge voltage
2.35 V/cell, equalized voltage
2.25 V/cell, float voltage
The backup time in the preceding table is for reference only.
The BOM number of the ESS-240V12-7AhBPVBA01 battery pack is 02310PFD.
The BOM number of the ESS-240V12-9AhBPVBA01 battery pack is 02310MWN.
Table 9-1
Backup time of the ESS-240V12-7AhBPVBA01 battery pack (6 kVA UPS; calculated
based on 94% battery efficiency)
Load (%)
Load (W)
One
Battery
Pack
(Min.)
Two
Battery
Packs
(Min.)
Three
Battery
Packs
(Min.)
Four
Battery
Packs
(Min.)
100%
5400
6
19
29
46
80%
4320
9
25
43
57
50%
2700
19
46
68
92
30%
1620
36
77
120
174