TP48200A-D17A5-2 Telecom Power
User Manual
A Technical Specifications
Issue 04 (2019-12-20)
Copyright © Huawei Technologies Co., Ltd.
58
A.3 EMC Specifications
Table A-3
EMC specifications
Item
Specifications
Electromagnetic
interference (EMI)
Conducted emission (CE)
Class A, EN300386
Radiated emission (RE)
Class A, EN300386
Harmonic current
EN61000-3-12
Voltage fluctuation and flicker
EN61000-3-11
Electromagnetic
susceptibility (EMS)
ESD
EN61000-4-2, criterion B
Contact discharge: 6 kV; air discharge: 8 kV
Electrical fast transient (EFT)
EN61000-4-4, criterion B
AC power port: ±2 kV; DC power port: ±2 kV;
signal port: ±1 kV
Radiated susceptibility (RS)
EN61000-4-3, criterion A
10 V/m
Conducted susceptibility (CS)
EN61000-4-6, criterion A
AC and DC power ports: 10 V; signal port: 3 V
Surge susceptibility
EN61000-4-5, criterion B
AC power port: ±2 kV in differential mode,
±4 kV in common mode, 8/20 µs
DC power port: ±2 kV in differential mode,
±4 kV in common mode, 8/20 µs
Signal port: 0.5 kV in differential mode, 1
kV in common mode, 8/20 µs
Voltage dip immunity (DIP)
EN61000-4-11
A.4 Cabinet Specifications
Table A-4
Cabinet specifications
Item
TP48200A-D17A5-2
Dimensions (H x W x D)
1760 mm x 650 mm x 700 mm (excluding the base)
Weight
< 200 kg (excluding rectifiers and batteries)
Protection level
IP55
Maintenance mode
Operated and maintained from the front