SUN2000-(50KTL-JPM0, 50KTL-JPM1, 63KTL-JPM0)
User Manual
7 Man-Machine Interactions
Issue 01 (2018-09-30)
Copyright © Huawei Technologies Co., Ltd.
81
No.
Parameter
Description
Unit Value Range
Remarks
2
Phase protection point The Japanese standard
requires that during passive
islanding detection,
protection should be
triggered if an abrupt
voltage phase change is
detected.
º
[3, 15]
N/A
3
Phase angle offset
protection
The standards of certain
countries and regions
require that the SUN2000
needs to be protected when
the three-phase angle offset
of the power grid exceeds a
certain value.
N/A
Disable
Enable
N/A
4
10 minute OV
protection
Specifies the 10-minute
overvoltage protection
threshold.
V
[1 x Vn, 1.4 x
Vn]
Vn represents the
rated voltage.
5
10 minute OV
protection time
Specifies the 10-minute
overvoltage protection
duration.
ms
[50, 7200000]
6
Level-1 OV
protection
Specifies the level-1
overvoltage protection
threshold.
V
[1 x Vn, 1.4 x
Vn]
7
Level-1 OV
protection time
Specifies the level-1
overvoltage protection
duration.
ms
[50, 7200000]
8
Level-1 UV
protection
Specifies the level-1
undervoltage protection
threshold.
V
[0.15 x Vn, 1 x
Vn]
9
Level-1 UV
protection time
Specifies the level-1
undervoltage protection
duration.
ms
[50, 7200000]
10
Level-1 OF protection Specifies the level-1
overfrequency protection
threshold.
Hz
[1 x Fn. 1.15 x
Fn]
Fn represents the
rated frequency.
11
Level-1 OF protection
time
Specifies the level-1
overfrequency protection
duration.
ms
[50, 7200000]
12
Level-1 UF protection Specifies the level-1
underfrequency protection
threshold.
Hz
[0.85 x Fn, 1 x
Fn]
13
Level-1 UF protection
time
Specifies the level-1
underfrequency protection
duration.
ms
[50, 7200000]