9 Alarm Management
Issue 03 (2015-01-05)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd
39
The battery loop is faulty.
Measures
1.
Check the battery circuit breaker. If the battery circuit breaker is OFF, rectify the battery
fault and switch on the battery circuit breaker.
2.
Check the battery cables and connectors, and replace faulty ones.
9.5.14 Rect Fault
Possible Causes
A rectifier is faulty.
Measures
1.
If the Fault indicator on a rectifier is steady red, reset the rectifiers one by one, if the
alarm persists, replace the rectifier.
9.5.15 Singl-Rect Fault
Possible Causes
Only one rectifier is faulty, and redundant rectifiers are provided.
Measures
If the Fault indicator on a rectifier is steady red,
reset the rectifiers one by one, if the alarm
persists, replace the rectifier.
9.5.16 Multi-Rect Fault
Possible Causes
Two or more than two rectifiers are faulty.
Measures
If the Fault indicator on a rectifier is steady red, reset the rectifiers one by one, if the alarm
persists, replace the rectifier.
9.5.17 Rect Comm Fault
Possible Causes
The signal cable to the rectifier is not connected properly.
The rectifier is removed.
The rectifier is in poor contact.