5 Operations
Issue 02 (2020-05-17)
Copyright © Huawei Technologies Co., Ltd.
69
The
BCB off
alarm (the red indicator is steady on) is displayed on the UPS LCD and
SmartLi LCD. No action is required. After the battery circuit breaker is switched on, the
alarm is automatically cleared.
After the BCU is started, the green indicator is on for 1s and then off for 4s.
If multiple SmartLi cabinets are combined, press and hold the POWER ON/OFF button on
the BCU of the master cabinet for more than 2 seconds to power on the master cabinet.
Then, power on slave cabinets one by one in the same way.
Step 3
Set the language, time, date, network parameters, and system parameters on the
Settings
Wizard
screen.
Figure 5-1
Settings wizard
Table 5-1
System Param.
Item
Description
Default
Value
Value Range
Battery cabinet
quantity
Specifies the total number of
combined cabinets.
1
1–8
EPO enable
EPO (emergency power-off) is
performed only when this
parameter is enabled and the
EPO switch is triggered.
When
EPO detection
is changed
from
Disable
to
Enable
, check
that the EPO cable is connected
correctly.
Disable
Disable, Enable
Battery cabinet
copper bar over
If this parameter is set to
Enable
,
an alarm is reported when the
Enable
Disable, Enable